Categories

LI2Y(St)CYSWAYÖ-uv-fl PIMF  *EMC
 - PE insulated, screened, data cable (300/500 V) Maximize

LI2Y(St)CYSWAYÖ-uv-fl PIMF *EMC
 - PE insulated, screened, data cable (300/500 V)

LI2Y(St)CYSWAYÖ-uv-fl PIMF *EMC
   PE insulated, screened, data cable (300/500 V) - Construction
 

Conductor            : tinned copper wires (7x0,30 mm SnCu).
Insulation             : PE comp., 2Y1.
PIMF construction  : polyester tape above the pair, AL-PES tape
                            over the drain wire (7 wires) 24 AWG stranded (7x32).
Lay-up                 : PIMF laid up in layers of optimum pitch.
Separator             : polyester tape.
Screen                 : with drain wire (7 wires) 24 AWG stranded
                            (7x32) under the AL-PES tape.
Screen                 : braid of tinned CU wires, 90% coverage.
Inner sheath         : PVC comp., 70° C.
Outer sheath         : PVC comp., UV and oil resistant.
Sheath colour       : RAL 7001, Grey.
*Electromagnetic compatibility

More details

LI2Y(St)CYSWAYÖ-uv-fl PIMF *EMC
   PE insulated, screened, data cable (300/500 V) - Technical data and tests
 
Rated voltage          :    0,22 mm² : 350 V;
                               ≥ 0,25 mm²: 500 V;
                               Uo/U  ≥  0,50 mm²: 300/500 V.
Test voltage            :     0,22 mm² : 1200 V;
                              ≥ 0,25 mm² : 1500 V;
                              ≥ 0,50 mm² : 2000 V.

Temperature range   : fixed    : - 30° C ~ + 70° C;
                              mobile :   - 5° C ~ + 70° C.
Min. bending radius : fixed    :   6 x D;
                              mobile : 15 x D.

Insulation resistance : min. 5000 MΩ/km.
Mutual capacitance  : d/d    0,22 mm²: max. 120 pF/m;
  d/d    0,25 mm²: max. 140 pF/m;
Inductance             : ~ 0,4 Mh/km;
Impedance : ~ 85 Ω.
 
LI2Y(St)CYSWAYÖ-uv-fl PIMF *EMC
   PE insulated, screened, data cable (300/500 V) - Standards


Cable                  : VDE 0812 & VDE 0814 & VDE 0245.

Conductor           : IEC 60228 Class 2; 

                           DIN EN 60228 Class 2.

Insulation            : VDE 0207-2  (2,20 mm).

Flame  test           : IEC 60332-1 & DIN EN 60332-1.

                            IEC 60332-3 & DIN EN 50266-2-4.
Sunlight resistance : UL 1581 section 1200.

Oil resistance         : ICEA S-82-552.
 
 
LI2Y(St)CYSWAYÖ-uv-fl PIMF *EMC
   PE insulated, screened, data cable (300/500 V) - Applications
 
This cable is used for low capacitance computer cable for RS-485 applications. These cables are recommended for direct burial.

All Rights Reserved Halley Cables © 2006 - 2024