Categories

J-Y(St)Y Lg - PVC insulated, screened, fire alarm installation cable Maximize

J-Y(St)Y Lg - PVC insulated, screened, fire alarm installation cable

J-Y(St)Y Lg  fire alarm installation cable - Construction
 

Conductor       : plain copper conductor, solid.
Insulation        : PVC compound , YI1; 

Lay-up            : pairs laid up in layers of optimum pitch.
                        * 2 pairs twisted as star-quad.
Screen            : tinned Cu drain wire under the AL-PES tape.

Drain wire Ø    : 0,40 mm ≤ 10 pairs;
  0,60 mm > 10 pairs.
Outer sheath  : PVC compound, YM1.
Sheath colour : RAL 7032, grey or RAL 3000, red.
Separator       : polyester tape.

More details

J-Y(St)Y Lg  fire alarm installation cable - Technical data and tests

Conductor resistance (loop) : 0,60 mm = 65 Ω/km;
  0,80 mm = 36 Ω/km.
Insulation resistance            : min. 100 MΩ/km.
Mutual Capacitance             : max. 100 nF/km (800 Hz).  * This value may be exceeded by 20% by cables with up to 4 pairs.
Capacity Unbalanced (k)      : 300 pF / 100 mt.  * 20% of the values, at least one value up to 500 pF permitted.
Operating voltage, peak      : max. 300 V.  * up to 600V permissible for short periods (6 s/min).
Test voltage                      : core / core & screen / core : 800 V.
Temperature range            : 30° C ~ + 70° C.
Min. bending radius            : 10 x D.
 
Core identification      : VDE 0815.

Conductor                : DIN EN 60228.

Flame retardance test: IEC 60332-1 & EN 50265-2-1.

Insulation                 : VDE 0207-4. 

Outer sheath            : VDE 0207-5.
 
J-Y(St)Y Lg  fire alarm installation cable - Applications
This installation cable can be used for fire alarm, in fixed installations within dry or damp premises, under or on plaster; it can also be used for fixed installations on external walls.
It must not be directly laid in ground or water, and it is not intended for supply purposes.
Furthermore this cable is suitable for applications at small bending radius.
The electrostatic screen protects transmission circuits against external disturbing electromagnetic impacts.