Categories

JE-H(ST)H BMK ...Bd FE180 E30 - Halogen free, fire resistant, telecommunication cable with FE180 and E30 Maximize

JE-H(ST)H BMK ...Bd FE180 E30 - Halogen free, fire resistant, telecommunication cable with FE180 and E30

Cable standard            : DIN VDE 0815.
Fire resistant               : EN 50266-2-4, EN 60332-1, IEC 60332-3 cat.C
Conductor                  : DIN EN 60228 class 1.
Insulation integrity       : DIN VDE 0472-814/ 8.83, 180 min.
Circuit integrity            : DIN 4102-12, VDE 0100-710 and 0100-718,
                                  30 min.
Peak operating voltage : 225 V.
Test voltage               : conductor/conductor and conductor/screen is
                                  800 V at 50 Hz. 
Temperature range      : fixed:-5° C till +50° C.  
                                   mobile:-30° C till +70° C.
Bending radius             : in motion is 7,5 x diameter.
Laying temperature      : -5° C...+50° C.
Insulation resistance     : min. 100 MOhm/km.

More details

These halogen free communication cables are intended for the installation in dry and moist areas, as well as in and under plaster. These installation cables are not accepted for power installation purposes and direct burial. They should be used in locations with fire hazard and where insulation integrity of at least 180 minutes and circuit integrity of at least 30 minutes are required.

All Rights Reserved Halley Cables © 2006 - 2024