N2XCH - Halogen free, fire retardant power cables with concentric conductor 0.6/1 kV Maximize

N2XCH - Halogen free, fire retardant power cables with concentric conductor 0.6/1 kV

Cable standard              : DIN VDE 0276-604, DIN VDE 0276-627.
Halogen free                : EN 50267-2-2, IEC 60754-2.
Fire retardant               : EN 60332-1-2, EN 60332-3-24.
Low smoke generation  : EN 61034.
Nominal voltage Uo/U    : 600/1000 V.
Test voltage                 : 4000 V (A.C.).
Service temperature      : -30° C till +90° C.
Bending radius              : min. 12 x diameter.
Laying temperature       : -5° C... + 90° C.

More details

These halogen-free cables are used as energy, utility and lighting cables in dry, moist and wet rooms, for permanent installation above, on, in and beneath plaster and also for outdoor applications where lots of human life and material assets need to be protected in industrial constructions, schools, hospitals, shopping and cultural centers, energy plants, airports, metros. In case of fire, these cables inhibit the propagation of the flames whereby the development of smoke is exremely low.  They must not be installed directly into the ground or into the water. No corrosive gases are emitted in the event of fire.