Categories

JE-H(ST)H FE180 E30 ...Bd - Halogen free and flame retardant installation cable with circuit integrity of 30 min Maximize

JE-H(ST)H FE180 E30 ...Bd - Halogen free and flame retardant installation cable with circuit integrity of 30 min

Cable standard                   : DIN VDE 0815.
Fire resistant                      : EN 50266-204, EN 60332-1,
                                         IEC 60332-3 cat. C.
Conductor                         : DIN EN 60228 class 1.
Insulation integrity              : DIN VDE 0472-814/ 8.83.
Circuit integrity                   : DIN 4102-12 according to VDE 0100-710
                                         and 0100-718.
Peak operating voltage       : 225 V.
Test voltage                      : conductor/conductor and conductor/screen is
                                         800 V at 50 Hz. 
Temperature range            : fixed :-5° C till +50° C.  
                                         mobile :-30° C till +70° C.
Bending radius                   : in motion is 7,5 x diameter.

More details

JE-H(ST)H FE180 E30 ...Bd installation cables are suitable for fixed installations in telecommunication. JE-H(ST)H FE180 E30 ...Bd should be used in locations with fire hazard and where insulation integrity of at least 180 minutes and circuit integrity of at least 30 minutes are required.