JE-H(ST)H FE180 E90 ...Bd - Halogen free and flame retardant installation cable with circuit integrity of 90 min Maximize

JE-H(ST)H FE180 E90 ...Bd - Halogen free and flame retardant installation cable with circuit integrity of 90 min

Cable standard              : DIN VDE 0815.
Fire resistant                 : EN 50266-204, EN 60332-1,
                                    IEC 60332-3 cat. C.
Conductor                    : DIN EN 60228 class 1.
Insulation integrity         : DIN VDE 0472-814/ 8.83 about 180 min.
Circuit integrity              : DIN 4102-12 according to VDE 0100-710
                                     and 0100-718.
Peak operating voltage   : 225 V.
Test voltage                 : conductor/conductor and conductor/screen is
                                    800 V at 50 Hz. 
Temperature range       : fixed:-5° C till +50° C.  
                                    mobile:-30° C till +70° C.
Bending radius              : in motion is 7,5 x diameter.
 

More details

JE-H(ST)H FE180 E90 ...Bd installation cables are suitable for fixed installations in telecommunication.  JE-H(ST)H FE180 E90 ...Bd should be used in locations with fire hazard and where insulation integrity of at least 180 minutes and circuit integrity of at least 90 minutes are required.