Categories

RE-2Y(St)H 70° C - CU/PE/OSCR/LSZH Maximize

RE-2Y(St)H 70° C - CU/PE/OSCR/LSZH

RE-2Y(St)H 70° C - CU/PE/OSCR/LSZH - PE insulated, collective screened, HFFR sheathed instrumentation cable 300 V
 
Construction

Conductor            : plain copper wire, stranded.

Insulation             : PE compound, (RE-2Y….).

Core identification : black / white cores numbered 1-1, 2-2,…
Upon request        : colour coded according to IEC 60189-2.

Triple                   : three conductors twisted to a triple.

Lay-up                 : triples laid up in layers of optimum pitch.

Separator             : polyester tape.

Screen                 : AL-PES tape over tinned copper drain
                              wire 0,50 mm².

Outer sheath         : HFFR compound.

Sheath colour        : RAL 9005, black or RAL 5015, blue.

More details

RE-2Y(St)H 70° C - CU/PE/OSCR/LSZH - PE insulated, collective screened, HFFR sheathed instrumentation cable 300 V
 
Technical Data and Tests
 
Rated voltage                   : 300 V.

Test voltage                     : Urms core-core     : 1500 V;

                                       Urms core-screen   : 1500 V.

Temperature range           : operation  : - 30° C ~ + 70° C;

                                      installation :  - 5° C ~ + 50° C.

Min. bending radius           : 7,5 x D.

Insulation resistance          : min. 5000 MΩ/km.

Capacitance unbalanced     : (1 kHz) : max. 500 pF/500 m.
 
RE-2Y(St)H 70° C - CU/PE/OSCR/LSZH - PE insulated, collective screened, HFFR sheathed instrumentation cable 300 V
 
Technical Data and Tests

Insulation thickness           : 0,50 mm² : 0,40 mm;
                                        0,75 mm² : 0,40 mm;

                                          1,0 mm² : 0,40 mm;

                                          1,3 mm² : 0,45 mm;
                                          1,5 mm² : 0,45 mm;

Conductor resistance          : 0,50 mm² : 36,7 Ω/km;

                                        0,75 mm² : 25,0 Ω/km;

                                          1,0 mm² : 18,5 Ω/km;
                                          1,3 mm² : 14,2 Ω/km;

                                          1,5 mm² : 12,3 Ω/km.

L/R (ratio) (max)                : 0,50 mm² : 25 µH/Ω;
                                         0,75 mm² : 25 µH/Ω;

                                           1,0 mm² : 25 µH/Ω;

                                           1,3 mm² : 40 µH/Ω;
                                           1,5 mm² : 40 µH/Ω.

Mutual capacitance (1 kHz):             ≤ 4 pairs                   all other pairs

                                         0,50 mm² : max. 115 pF/m,   max. 90 pF/m;

                                         0,75 mm² : max. 115 pF/m,   max. 90 pF/m;

                                           1,0 mm² : max. 115 pF/m,   max. 90 pF/m;

                                           1,3 mm² : max. 120 pF/m,  max. 105 pF/m;

                                           1,5 mm² : max. 120 pF/m,  max. 105 pF/m.

RE-2Y(St)H 70° C - CU/PE/OSCR/LSZH - PE insulated, collective screened, HFFR sheathed instrumentation cable 300 V
 
Standards

Design                : DIN EN 50288-7.

Conductor           : IEC 6022 class 2, DIN EN 60228 class 2.

Insulation            : EN 50290-2-23.

Outer sheath        : EN 50290-2-27. 

Flame retardancy  : IEC 60332-1 & DIN EN 60332-1;
                           IEC 60332-3 & DIN EN50266-2-4.

Halogen-free test  : IEC 60754-1/2;

                           DIN EN 50267-2.

Smoke density test: IEC 61034-2 & TS/DIN EN 61034-2.

RE-2Y(St)H 70° C - CU/PE/OSCR/LSZH - PE insulated, collective screened, HFFR sheathed instrumentation cable 300 V
 
Applications

These cables are used for transmission of analogue and digital signals in instrumentation and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc...
These cables are used in the environments which have no corrosive gases are emitted in the event of fire.
In case of fire, these cables inhibit the propagation of the flames whereby the development of smoke is extremely low.
Instrumentation cables are not allowed for direct connection to a low impedance sources, e.g. public mains electricity supply.
With blue sheath it is suitable for intrinsically safe systems.
These cables are not recommended for direct burial.
They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.

All Rights Reserved Halley Cables © 2006 - 2024