Categories

H07VVH6-F
 - PVC flat cable that can be subjected to a medium level of mechanical stress Maximize

H07VVH6-F
 - PVC flat cable that can be subjected to a medium level of mechanical stress

H07VVH6-F
 PVC flat cable - Construction

1. Conductor          : fine-stranded bare copper.

2. Core insulation    : polyvinylchloride (PVC), cores are laid up parallel.

3. Outer sheath      : soft polyvinylchloride (PVC), black.

More details

H07VVH6-F
 PVC flat cable - Technical data and tests

Nominal voltage Uo/U     : 450 / 750 V.

Test voltage                 : 2500 V (AC).

Temperature range        : motion   :   -5° C to +70° C;

                                     fixed      : -30° C to +70° C.

Operating temperature   : 160° C (short circuit).

Short circuit time           : 5 seconds max.

Bending radius               : min. 10 x diameter.

 

Cable standard              : DIN VDE 0281-404.

Construction                 : DIN EN 60228 class 5. 

Core identification          : HD 308 S2.

Flammability                  : EN 60332-1-2.
 
H07VVH6-F
 PVC flat cable - Applications
This cable should be used in dry and humid locations and not in open-air; it can withstand low and medium level mechanical loads.
This cable is suitable for connecting movable parts of machine tools, material handling equipment and large machines as long as it is exposed to bending in only one plane.
Cables with more than 5 cores grouped with individual groups are separated by a stay. 