ACYAbY / ACYAbY-F low voltage power cable 0.6/1 kV - Technical data and tests
Conductor type : monowire (re), multiwire (rm).
Rated voltage Uo/U : 0.6/1 kV.
Test voltage : 3.5 kV AC or 8.4 kV DC,5 min.
Min. temperature of cable : installation : -5º C.
operation : -30º C.
Max. allowed operating temperature : 70º C.
Max. short-circuit temperature : 160º C.
Min. bending radius : 12 x cable diameter with more than 1 conductors.
15 x cable diameter with 1 conductor.
Max. tensile strain during installation : max 50 N/mm².
Color coding : 1 conductor-blue or yellow-green;
2 conductors - blue,brown;
- yellow-green,black for sect > 10 mm²;
3 conductors - brown,black,grey;
- yellow-green, blue,brown;
4 conductors - blue, brown, black,grey;
- yellow-green, brown,black,grey;
5 conductors - blue, brown, black, grey, black;
- yellow-green, blue, brown, black,grey;
More than 5 conductors: - numbered black conductors;
- yellow-green and numbered conductors.
Cable : IEC 60502-1.
Conductors : IEC 60228.
Insulation : IEC 60502-1.
Flame retardancy: ACYAbY : EN 50265-2-1 (IEC 60332-1) - burning on a single vertical cable.
ACYAbY-F : EN 50266-2-4 (IEC 60332-3-25 Cat. C) - burning on a bundle of cables.
ACYAbY /
ACYAbY-F low voltage power cable 0.6/1 kV - ApplicationsThis cable is used to transmit the power supply to power stations. It must be protected against: corosive chemicals, chemical solvents and solar radiation. This cable can be installed underground, in air, inside or outside and has a high resistance to mechanical shocks. This is a flame retardant cable. ACYAbY / ACYAbY-F low voltage power cable 0.6/1 kV - Other standardsBritish : AL/PVC/STA/PVC.German : NAYBY.Russian : АВБбШв.
Turkish : YAVZ4V-R.Central Europe : PP 41-A.