Categories

HYC-FLEX - Low voltage very flexible copper power cable with PE insulation Maximize

HYC-FLEX - Low voltage very flexible copper power cable with PE insulation

HYC-FLEX low voltage power cable - Construction


Conductor          : 3 conductor: bare copper, round, stranded, class 5.
  
                          5 conductor: bare copper, round, stranded.

Insulation           : elastomer.

Inner covering    : extruded filling compound with release tape to bond.

Outer conductor : 3 conductor: copper wires, ceander shaped,
                          with Cu-counter helix.
  
                          5 conductor: protective earth (PE) Cu wires, ceander
                          shaped, with Cu-counter helix.

Outer sheath      : halogen-free, durable PE.

More details

HYC-FLEX low voltage power cable -Technical data and tests

Core identification                      : 3 conductor: 3LPEN: L1 black, red L2, L3 white. 
        
                                                                   2LNPE: L1 black, brown L2, N blue.
  
                                                 5 conductor: L1 brown, black L2, L3 gray, blue N.

Abrasion resistant identification     : 2 yellow longitudinal stripes, year / month, cable marking, 0.6 / 1 kV, meter marking.

Rated voltage Uo/U                    : 0,6/1 kV.

Test voltage (AC voltage, 5 min)  : 3.5 kV.

Temperature range                    : continuous operation: ≤ 90° C.

                                                 emergency operation (less than 8 h / d, less than 100 h / a) : ≤ 130° C.
  
                                                 short circuit: ≤ 250° C.


Cable standard                              : CENELEC HD 601 S1 part 7E.


Test voltage (AC voltage, 5 min)     : HD 603.1
Conductor                                    : IEC 60228.

Halogen free                                 : IEC 60 754-1.

No corrosive gases                         : DIN EN 50 267-2-3.

No toxic gases                              : DIN EN 50 305.

Insulation                                     : HD 603.1 Table 2B.

Conductor resistance (DC at 20° C) : IEC 60228.

Core identification                         : 3 conductor : HD 603 S1 part 7E.
  
                                                   5 conductor : HD 308.

The cables comply with EU LVD (low voltage directive 73/23/EEC) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH), dated 20.06.2013.
 


HYC-FLEX low voltage power cable - Applications

Suitable for use in soil, conduits, cable ducts and outdoors for power stations, industry and switchgear as well as in low voltage distribution networks.
The design is specifically used in the 5-conductor system TN-S with a separate neutral conductor (N) and protective earth (PE).
This enables EMC optimized supply network to reduce the electromagnetic interference.

By the networked conductor insulation particularly suitable for higher temperatures for short-circuit and overload.
The PE sheath of the network cable is particularly robust and is characterized by excellent mechanical properties and increased resistance to heat pressure.

All Rights Reserved Halley Cables © 2006 - 2024