Categories

ACYY / ACYY-F  Low voltage, aluminium conductor, PVC insulated and sheathed cable (0.6/1 kV) Maximize

ACYY / ACYY-F Low voltage, aluminium conductor, PVC insulated and sheathed cable (0.6/1 kV)

ACYY / ACYY-F  low voltage power cable 0.6./1 kV - Construction

1. Conductor     : aluminium, solid or stranded.

2. Insulation      : PVC type DIV 4.

3. Filling.

4. Outer sheath : PVC type DMV 5 black or grey.

More details

ACYY / ACYY-F  low voltage power cable 0.6./1 kV - Technical data and tests
Rated voltage Uo/U                   : 0.6/1 kV.

Test voltage                             : 4 kV AC or 12 kV DC, 5 min.

Min. cable temperature              : installation : -5º C.

Max.permissible operating temp.  :   70º C.

Max. short-circuit temperature     : 160º C.

Min. bending radius at installation : 15 x cable diameter – single-core cable;
  
                                                12 x cable diameter – multicore cable.

Max. tensile strain during instal.    : max. 50 N/mm².
 

Cable standard   : HD 603 S1/3G-2; IEC 502.

Conductor type  : class 1 or 2, according to EN 60228.

Flame retardancy: ACYY    : EN 50265-2-1 (IEC 60332-1) - flames on a single vertical cable.
  
                         ACYY-F  : EN 50266-2-4 (IEC 60332-3-24 Cat. C) - flames on a bunch of cables.
 
ACYY / ACYY-F  low voltage power cable 0.6./1 kV - Applications

ACYY / ACYY-F is a cable for power supply to power stations. This cable can be installed in open or confined areas, underground (in pipes), in sewers, in concrete, in places where no mechanical damage is expected.
 
ACYY / ACYY-F  low voltage power cable 0.6./1 kV - Other standards
British             : AL/PVC/PVC.
German           : NAYY.
Austrian           : E-AYY.
Russian            : АВВГ.
Central Europe : PP 00-A.
Turkish            : YAVV-R.