NYY - J/-O low voltage power cable - Construction


Conductor material      : bare copper, class 1,
                                  from 25 mm² class 2.
Insulation                   : PVC DIV 4.
Sheathing material       : PVC DMV 5.
Colour of outer sheath : black.
UV-resistant                : yes.

More details

NYY - J/-O low voltage power cable - Technical data and tests
Nominal voltage Uo/U                   : 0.6/1 kV.

Maximum permitted operating

voltage in 3-phase systems            : 1,2 kV. 

Test voltage                               : 4 kV. 

Max. temperature at conductor     : 70° C.
Max. operating temperature, fixed : 70° C.
Temp., moved/during installation   : -5° ... +70° C.
 

Cable standard     : VDE 0276 (HD 603).

Core identification: VDE 0293 (HD 308).

Conductor          : DIN EN 60228.

Flame retardant   : VDE 0482-332-1-2 / IEC 60332-1.
 
NYY - J/-O low voltage power cable - Applications
This distribution and signal power cable is for static outdoor applications (with protection against direct UV-irradiation), in ground, in cable canals, in water, within facilities, in concrete, in conditions where heavier mechanical loads and specially tensile strains, are not expected.
It is often used in transformer stations, electric power plants, industrial plants, metropolitan networks and in other electric plants, same as for connection of signalling devices in industry, traffic and similar.
The normal minimum installation depth is 0.6 m, but is should be at least 0.8 m under roads.
In concrete it should be buried at a temperature below the maximum cable operating temperature of +70 °C according to the VDE standard HD 603/VDE 0276-603 governing PVC cables for direct burial.
When submerged underwater, the cable should not stay longer than 2 weeks at a time, maximum submersion depth being 10 metres, and it should be installed only in static water/bodies of water without shipping traffic.
 
NYY -J/-O low voltage power cable 0.6/1 kV - Other standards
British                  : CU/PVC/PVC.
German               : NYY.
Austrian              : E-YY.
Russian               : ВВГ.
Central Europe : PP 00.
Turkish                : YVV-U.