Categories

FY - H05V-U (0.3/0.5 kV) - H07-U (-R) (0.45/0.75 kV) - unsheathed single core copper Maximize

FY - H05V-U (0.3/0.5 kV) - H07-U (-R) (0.45/0.75 kV) - unsheathed single core copper

FY - H05V-U - H07V-U (-R) - Construction


Conductor material : copper, rigid annealed monowire (ru) - H05V-U,
                             H07V-U - or rigid multiwire (rm) - H07V-R. 

Insulation              : PVC type TI1.

More details

FY - H05V-U - H07V-U (-R) - Technical data and tests

Nominal voltage Uo/U               : 300/500 V; 50 Hz; 
  450/750 V; 50 Hz.

Max. temperature at conductor : +70° C.

Max. short circuit temperature   : +160° C for 5 seconds.

Min. bending radius                  : 6 x cable diameter.

Color coding                           : H05V - Monochrome cables: black, blue, brown, gray,
                                                        orange, pink, red, tourquoise, violet, white, green and yellow.
                                                        All two-colors combinations are accepted.
                                                        Yellow-green cables : min 30% green, max 70% yellow.

                                             H07V -  Monochrome cables: black, blue, brown, gray, orange, pink, red,
                                                        tourquoise, violet, white
                                                        Yellow-green cables : min 30% green, max 70% yellow.
                                                        Other two-colors combinations are not accepted.
 
HD 21.3 S3
.
HD 21.3+A1.

IEC 227/3
.
EN 60228.
 
FY - H05V-U - H07V-U (-R) - Applications

For laying in pipes on top of or under plaster and in closed installation ducts and for internal wiring of machinery, switchgear and distributor systems.
The cable is not suitable for direct laying under plaster, however, only for signal circuit and control circuit.