YQY-fl - Low voltage, PVC insulated, armoured and PVC sheathed power cable (0.6/1 kV) Maximize

YQY-fl - Low voltage, PVC insulated, armoured and PVC sheathed power cable (0.6/1 kV)

YQY-fl low voltage power cable (0.6/1 kV) - Construction


Conductor       : copper wires, stranded.
Insulation        : PVC compound, DIV4.
Lay-up            : cores laid up in layers for optimum pitch.
Filler               : PVC filler compound, BLACK.
Armour           : braided galvanized steel wires, aprox. 85 % optical coverage.
Outer sheath   : PVC compound, DMV5.
Sheath colour  : RAL 9005, Black


More details

YQY-fl low voltage power cable (0.6/1 kV)  - Technical data and tests

Rated voltage Uo/U           : 0,6 / 1 kV.
Test voltage (AC 50 Hz)     : 3,5 kV. 

Temperature at conductor : 90° C.
Temperature range           : fixed : - 30° C  ~  + 70° C.
Min. bending radius            : ≤ 16 mm² : 6 x D.
                                        ≥ 25 mm² : 8 x D.
 
Cable                   : DIN VDE 0276-627, HD 627 S1 & IEC 60502-1.

Conductor            : IEC 60228 Cls. 2, DIN EN 60228 Cls.  2.

Insulation             : HD 603 S1.

Core identification : HD 308 S2 & VDE 0293-308.

Flame testing        : IEC 60332-1-2.

Outer sheath        : HD 603 S1.
 
YQY-fl low voltage power cable (0.6/1 kV) - Applications
These armoured power and control cables are used indoors and outdoors, in cable ducts, industrial plants, in power, switching plants and underground applications where there is no risk of mechanical damage.