Categories

U-1000 AR2V - XLPE insulated, aluminium conductor, PVC outer sheath, installation and power cable (0.6/1 kV) Maximize

U-1000 AR2V - XLPE insulated, aluminium conductor, PVC outer sheath, installation and power cable (0.6/1 kV)

U-1000 AR2V power cable 0.6/1 kV - Construction


Conductor                                 : aluminium rigid compact, class 2.
Insulation                                  : XLPE crosslinked polyethylene.

Outer sheath                             : PVC.
Screen                                      : no

Drain wire                                  : no

Lead sheath                               : no

Concentric conductor                  : none

Armouring                                  : no

Halogen free (acc. EN 50267-2-2) : no

Low smoke (acc. EN 61034-2)      : no

Insulation integrity                      : no

Circuit integrity                           : no

More details

U-1000 AR2V power cable 0.6/1 kV - Technical data and tests
Standards                            : NFC32-321 C32-321/A1; IEC 60502-1; NF EN 60332-1-2; NF C 15-100.

Flame retardant                    : acc. EN 50265-2-1.
Nominal voltage U0/U            : 600/1000 V.
Test voltage (50 Hz)             : 4000 V.
Maximun voltage Um             : 1200 V.
Maximun operating temp.      : +90° C.
Maximun short circuit temp.   : +250° C.
Min. operating temperature 

(without mechanical shocks)  : -25° C.
Minimum installation 
and
use temperature                  : -10° C.
Minimum bending radius 
per D
cable diameter (in mm)         : 8 x D.
Maximum pulling stress          : 50 N/mm² (of aluminium cross section).
Core colours                        : single core : black;

                                           two cores : blue-brown;
                                           three  cores : brown-black-blue  (1,5/2,5mmq);  
                                           brown-black-gray  (4mmq)  or Y/G-blue-brown);
                                           four cores : blue-brown-black-gray (or Y/G instead blue);
                                           five cores : blue-brown-black-gray-Y/G (or black instead Y/G).
Sheath colour                      : black.

U-1000 AR2V power cable 0.6/1 kV - Applications
This cable is for use on industrial sites and upright columns of buildings. Particularly suited in cases of high operating temperatures and when high resistance to solar radiation and atmospheric agents is required. Good resistance to low temperatures and chemical agents.
It can be used without additional mechanical protection in the open air, fixed to walls or in raceways, inside walkways, and in empty in constructions in general. It can be laid undrground with mechanical protection constructed from slabs, tiles, or bricks.
It is not recommended to lay this cable in the ground, flooded for more than two months per year.
With appropriate mechanical protection it can be used in areas subject to risk of explosion, but in this case the permitted current load is reduced by 15%.

U-1000 AR2V power cable 0.6/1 kV - Other standards
German   : NA2XY.
British      :  AL/XLPE/PVC.
Serbian    : XP 00-A.
Turkish    : YAV-U (-R).
Romanian : AC2XY

All Rights Reserved Halley Cables © 2006 - 2024