U-1000 R2V - XLPE insulated, copper conductor, PVC outer sheath cable Maximize

U-1000 R2V - XLPE insulated, copper conductor, PVC outer sheath cable

U-1000 R2V - Construction

Conductor            : rigid red copper wire, class  1 (ø ≤ 4 mm²).
                            stranded circular compacted copper class 2 (ø>4mm²)
Insulation             : XLPE crosslinked polyethylene (no dry cool). 

Outer sheath        : PVC.
Screen                 : no

Drain wire             : no

Lead sheath          : no

Concentric cond.   : none

Insulation integrity : no

Circuit integrity      : no

Armouring            : no

More details

U-1000 R2V - Technical data and tests

Standards                                   : NF C 32-321 C32-321/A1; IEC 60502-1 NF EN 60332-1-2; NF C 15-100.

Nominal voltage U0/U                   : 0,6/1 kV.
Test voltage (50 Hz)                    : 4 kV.
Maximun voltage Um                     : 1,2 kV.
Maximun operating temperature     : +90° C.
Maximun short circuit temperature  : +250° C .
Min. operating temperature 
  
(without mechanical shocks)          : -25° C.
Minimum installation and use temp. : -10° C.
Minimum bending radius per 
  
D cable diameter (in mm)             : 6 x D.
Maximum pulling stress:                : 5 kg/mm² (of copper cross section).
Core colours                               : single core    : black. 

                                                  two cores    : blue-brown.
                                                  three  cores : brown-black-blue  (1,5/2,5 mmq);
                                                                      brown-black-gray (4 mmq)  or Y/G-blue-brown).
                                                  four cores    : blue-brown-black-gray (or Y/G instead blue).
                                                  five cores     : blue-brown-black-gray-Y/G (or black instead Y/G).
Sheath colour                             : black.

U-1000 R2V - Applications
This cable is for use on industrial sites and the upright columns of buildings. Particularly suited in cases of high operating temperatures and when high resistance to solar radiation and atmospheric agents is required.
Presents good resistance to low temperatures and chemical agents. It can be used without additional mechanical protection in open air, fixed to walls or in raceways, inside walkways, and in empty in constructions in general.
It can be laid underground with mechanical protection constucted from slabs, tiles, or bricks. It is not recommended to lay this cable in ground flooded for more than two months per year.
With appropriate mechanical protection it can be use in areas subject to risk of explosion, but in this case the permitted current load is reduced by 15%.
U-1000 AR2V power cable 0.6/1 kV - Other standards
German   : N2XY.
British      :  CU/XLPE/PVC.
Serbian    : XP 00.
Turkish    : YXV-U (-R).
Romanian : C2XY.