Categories

N2XS(FL)2Y 
- Medium voltage copper power cable with XLPE insulation Maximize

N2XS(FL)2Y 
- Medium voltage copper power cable with XLPE insulation

N2XS(FL)2Y 
medium voltage copper power cable - Construction


1. Stranded bare copper.
2. Inner semi-conductive layer.
3. XLPE insulation (cross-linked polyethylene).
4. Outer semi-conductive layer.
5. Semi-conductive swellable tape.
6. Copper wire screen.
7. Swellable tape ensuring longitudinal and radial water seal.
8. PE coated aluminium tape.
9. PE outer jacket.

More details

N2XS(FL)2Y 
medium voltage copper power cable - Technical data and tests

Rated voltage                                   : 6/10 kV; 12/20 kV; 18/30 kV; 20,8/36 kV.

Cable standard                                  : DIN VDE 0267-620.

Operating temperature, short circuit    : 250° C.

Max. conductor temperature in service :   90° C.

Minimum installation temperature         :  -20° C.

Halogen free                                     : EN 60332-1.

Lead free.

UV stability.
 
N2XS(FL)2Y 
medium voltage copper power cable - Applications

N2XS(FL)2Y - 6/10 kV; 12/20 kV; 18/30 kV; 20,8/36 kV - medium voltage power cable is for static application in ground, within and outside facilities, outdoor, in cable canals, in dry areas or in water.
PE sheath secures increased mechanical resistance during and after laying. Swellable tape blocks water spreading within the cable.
Due to its very low factor of dielectric loss, which remains constant over its entire operating lifetime, and owing to excellent insulation property of XLPE-material, firmly longitudinally spliced with inner and external screen of semi-conductive material (extruded in one process), the cable has a high operating reliability.
This cable can be used in switching blocks, transformer stations, industrial plants and in electric power plants.
To avoid the effects of external impact, the adhering semi-conductive layer extruded between conductor and insulation, along with concentric copper conductor, secures restriction of electric field and resistance to partial discharges. 
 
N2XS(FL)2Y 
medium voltage copper power cable - Other standards
British       : CU/XLPE/CWS/LW/PE
Poland      : XRUHKXS
Russia       : ПвПу2г
Ukraine     : ПвЭгаПу

All Rights Reserved Halley Cables © 2006 - 2024