RG7H1M1 medium voltage power cable - Construction
Conductor      : red copper, rigid, class 2.

Inner sheath   : semi-conducting material.
Insulation       : HEPR having G7 quality*.
Outer layer     : semi-conducting layer, special high module HEPR.

Shield            : red copper wire.
Outer sheath : thermoplastic sheath in M1 quality, HFFR.

Colour           : red.

More details

RG7H1M1 medium voltage power cable - Technical data and tests

Nominal voltage Uo/U             : 12 /20 kV (AC).

Test voltage (50 Hz)              : 42 kV.

Maximum voltage Um              : 24 kV.

Max. operating temperature    : 105° C.

Max. short circuit temp.          : 300° C.

Min. operating temperature

(without mechanical shocks)    : -20° C.

Min. installation and use temp. : -5° C.

Minimum bending radius 

per D cable diameter (in mm)  : 12 x D; 

Maximum pulling stress            : 60 N/mm².



* G7 - Suitable for cables showing high electrical and mechanical performances, fire resistance, LS0H cable core. Working temperature: -60 + 90°C. This compound is halogen free.
 
IEC 60502
.
CEI 20-13.

CEI EN 50266-2-4 (CEI 20-22 III)
.
CEI EN 60332-1-2
.
CEI EN 50267-2-1.

CEI EN 61034-2
.
The cable meets the requirements according to HD 620 for insulation, for all other characteristics compared to CEI 20-13.
 
RG7H1M1 medium voltage power cable - Applications

This cable is suitable for the transportation of energy between the substations and large users.
It is particularly suitable in areas with danger of fire equipment on the premises where they are concentrated, frameworks and tools where it is essential to safeguard them.
There is no problem if it is left for free-hanging, or installed in tube or channel.
Laying underground should be made in accordance with Art. 4.3.11 of IEC 11-17.