Categories

TA2X(FL)2Y
 - Triple core medium voltage power cable Maximize

TA2X(FL)2Y
 - Triple core medium voltage power cable

TA2X(FL)2Y
 power cable - Construction

1. Conductor : aluminium stranded conductor, round, compacted, class 2.
2. Screen      : extruded semiconductor.
3. Insulation  : XLPE.
4. Screen      : extruded semiconductor.
5. Tape        : semiconducting material, water repellent.
6. Tape        : aluminum with copolymer,
                    thickness 0.185 mm and adhesive to the PE sheath.
7. Sheath     : medium density PE jacket, weatherproof.

More details

TA2X(FL)2Y
 power cable - Technical data and tests
Max. conductor temp. for optimal operation    :  +90° C.
Max. short-circuit temperature (max. 5 s)       : +250° C.
Minimum installation temperature                   :   -20° C.
Minimum operating temperature                    :   -40° C.
Test voltage                                               : 21 kV for cables of 6/10 kV;
                                                                  42 kV for cables of 12/20 kV;
                                                                  63 kV for cables of 18/30 kV.

Peak pulling force during installation               : max. 30 N/mm² per conductor cross-section.

Partial discharge level at 1.73 Uo                   : max. 2 PC.

Bending radius                                            : single-core : 15 x D where D is the outer diameter of the core.
                  
                                                                  triple-core  : 12 x D where D is the external diameter of the core.

Notes                                                        : in the event of a single bend, for example into enclosures, electrical panels,
                                                                  a single bending radius two times smaller than the regular size is permitted with
                                                                  the condition to be carefully bent, at 20-30° C and following a template.

TA2X(FL)2Y
 power cable - Standards
Conductor              : according to EN 60228.

Insulation               : according to CEI 60502-2.  

Reference standard : NF C 33-223.

TA2X(FL)2Y
 power cable - Applications
This cable is designed for the construction of medium voltage lines. It is transversally and longitudinally waterproof and it can be installed in air, ground or water.

All Rights Reserved Halley Cables © 2006 - 2024