Categories

H07RN-F 
MULTIWIRE - Rubber insulated multicore flexible cable for indoor and outdoor use Maximize

H07RN-F 
MULTIWIRE - Rubber insulated multicore flexible cable for indoor and outdoor use

H07RN-F 
MULTIWIRE rubber insulated cable - Construction
 
Conductor      : bare flexible copper.

Insulation       : E14 quality rubber.

Outer sheath   : polychoroprene EM2 quality or equivalent.

Sheath colour : black.

More details

H07RN-F 
MULTIWIRE rubber insulated cable - Technical data and tests
Rated voltage Uo/U                    : 450/750 V.

Test voltage                              : 2,5 kV.

Min. ambient temperature            :  - 40° C ~ -15° C.

Maximum operating temperature   : + 60° C.

Min. laying temperature               :  - 25° C.

Short circuit temperature             : + 200° C.

Min. bending radius                    : 4 X D ~ 6 X D.

UV resistant                               : yes.

Ozone resistant                          : yes.

Oil resistant                               : yes.

Flame retardant                          : yes.
 
H07RN-F 
MULTIWIRE rubber insulated cable - Standards
EN 50525-2-21.

CENELEC HD 22.4 S3.

CEI 20-19 p.4.
 
H07RN-F 
MULTIWIRE rubber insulated cable - Applications

Rubber-insulated multicore flexible cable with polychloroprene sheathing suitable for connecting signalling and control gear.
The conductors are Black insulated with white numbers and a Green/Yellow earthing conductor.
The manufacturing technique and the quality of the materials involved make this cable particularly reliable in terms of operating safety and long life, even in temperature ranges from -40° C (in static conditions) up to +60° C.
It can be used for indoor and outdoor applications and in damp or wet environments.
The neoprene protective sheathing makes it resistant to oils, weathering and mechanical stresses.
Laying underground is only acceptable if adequate protection is provided against the risk of damage.
During laying and wiring operations, avoid exceeding a tensile strain of 5 Kg x mm² of the total conductor's area.
Not recommended for connecting equipment subject to continuous movements, supplied by means of catenaries or cable-winder drums.

All Rights Reserved Halley Cables © 2006 - 2024