Categories

H05RR-F - Flexible, EPR rubber insulated and sheathed cable Maximize

H05RR-F - Flexible, EPR rubber insulated and sheathed cable

H05RR-F cable for installations - Construction

Conductor      : flexible copper, class 5.

Insulation       : elastomeric mixture (EPR) insulation of EI4 quality.

Outer sheath   : polichloroprene (EPR) sheath, EM2.

Sheath colour : black.

More details

H05RR-F cable for installations - Technical data and tests

Nominal voltage Uo/U                : 300/500 V.

Test voltage                             : 2000 V.

Maximum operating temperature  : +60° C.

Max. short circuit temperature     : +200° C.

Min. operating temperature         : -40°C (no mechanical shocks).

Min. installation and use temp.    : -25°C.

Max. pulling stress                     : 15 N/mm².

Min. bending radius                   : fixed lay  : D<8=3; D<12=3D; D>12=4D.
  
                                                free move: D<8=4D; D<12=4D; D>6D.
 
H05RR-F cable for installations - Standards
BT 2006/95/EC- RoHS: 2002/95/EC.
CEI EN 50525-2-21.

CEI 20-107/2-21.

CEI 20-19/4 (CENELEC HD 22.4 S4).

BS 7919:2001.

NF C 32-102-4.

VDE 0282-4.

CEI EN 60332-1-2 (CEI 20-35).

BS EN 60332-1-2.

NF EN 60332-1-2.

DIN EN 60332-1-2.
 
H05RR-F cable for installations - Core identification
Single core  : black.
Two cores   : blue-brown.
Three cores : brown-black-gray (or blue-brown-Y/G).
Four cores   : blue-brown-black-gray (or Y/G instead blue).
Five cores    : Y/G-blue-brown-black-gray (black no Y/G).
 
H05RR-F cable for installations -  Applications
These cables are meant for general usage in domestic areas, kitchens, offices and to feed portable devices submitted to weak mechanical stresses, exhaust fans, ktichen appliances, irons for welding, toasters and many other appliances and purposes.
Unsuitable for permanent outdoor use, undeground, for applications in industrial workshops or for supplying other than domestic electric tools.

All Rights Reserved Halley Cables © 2006 - 2024