Categories

HSLH
 - Control cable with flexible copper wires and HFFR sheath 0.6/1 kV Maximize

HSLH
 - Control cable with flexible copper wires and HFFR sheath 0.6/1 kV

HSLH
 control cable 0.6/1 kV - Construction


Conductor            : flexible copper wires, plain.
Insulation             : HFFR compound, TI6.
Core identification  : coloured cores or numbered cores
Lay-up                 : cores laid up in layers of optimum pitch
Outer sheath        : HFFR compound, TM7.
Sheath colour       : RAL 9005, Black.

More details

HSLH
 control cable 0.6/1 kV - Technical data and tests

Insulation resistance           : min. 50 MΩ/km.
Rated voltage    Uo/U         : 0,6/1 kV.
Test voltage (AC 50 Hz)      : 4 kV.
Temperature range            : fixed    : - 30° C  ~  + 70° C.  

                                         mobile :  -  5° C  ~  + 50° C.  
Short circuit temp. on core : 160° C.
Min. bending radius            : fixed    :   8 x D.

                                         mobile : 15 x D.
HFFR                                : halogen-free flame retardant
 

Cable standard             : VDE 0245-20. 

                                   (Designed according to)
  
                                   HD 21.14 S1 & HD 21.13 S1.

Conductor                   : IEC 60228 Class 5, DIN EN 60228 Class 5.

Insulation                    : DIN EN 50367-7.

Outer sheath               : DIN EN 50367-8.

Smoke density             : IEC 61034-2 & DIN EN 61034-2.

Halogen-free properties : IEC 60754-1/2 & DIN EN 50267-2.
Flame test                   : IEC 60332-3 & DIN EN 50266-2-4.
 
HSLH
 control cable 0.6/1 kV - Applications
These  flexible cables must be used as energy or connecting cables in mechanical engineering for applications such as: instrumentation and control equipment for tooling machinery production lines and flexible applications for free movement with low tensile load.
These cables with copper screening are ideally suitable for interference-free data and signal transmission in measuring and control technology.
These cables are used for outdoor installation and are not recommended for direct burial.

All Rights Reserved Halley Cables © 2006 - 2024