Construction


Conductor            : plain annealed copper wire, BS 6360 0,50 mm²
                            and 0,75 mm² flexible, or 1,5 mm² stranded.

Insulation             : PVC compound, TI1, BS 6746.


Pair                      : two conductors twisted to a pair.

PIMF construction  : polyester tape above the pair,
                             AL-PES tape over tinned copper drain wire, 0,50 mm².


Separator             : polyester tape.

Screen                 : AL-PES tape over tinned copper drain wire 0,50 mm².

Outer sheath        : PVC compound, flame retardant; TM1, BS 7655.

Sheath colour       : RAL 9005, black.

More details

RE-Y(St)Y-PIMF   70° C - 
CU/PVC/ISCR/OSCR/PVC - Multi-pair, PVC insulated, individual and collective screened, PVC sheathed instrumentation cable 300/500 V
 
Technical Data and Tests
 
Rated voltage  (U°/U)           : 300/500 V.

Test voltage                        : Urms core-core    : 1000 V;
                                           Urms core-screen : 1000 V.

Temperature range               : operation : - 40° C ~ + 70° C;
                                        
   installation : - 5° C ~ + 50° C.

Min. bending radius             : 6 x D.

Insulation resist. (20° C)      : min. 25 MΩ/km.

Mutual capacitance              : max. 250 pF/m (1 kHz).

Capacitance unbalanced       : (1 kHz) : max. 450 pF/250 m.

RE-Y(St)Y-PIMF   70° C - 
CU/PVC/ISCR/OSCR/PVC - Multi-pair, PVC insulated, individual and collective screened, PVC sheathed instrumentation cable 300/500 V
 
Technical Data and Tests


L/R (oran-ratio) (max)    : 0,50 mm² : 25 µH/Ω;
                                    0,75 mm² : 25 µH/Ω;
                                      1,5 mm² : 40 µH/Ω.

Insulation thickness        : 0,50 mm² : 0,60 mm;
                                     0,75 mm² : 0,60 mm;
                                     1,50 mm² : 0,60 mm.

Conductor class, BS 6360: 0,50 mm² : Class 5;
                                     0,75 mm² : Class 5;
                                       1,5 mm² : Class 2.

Conductor resist.(20° C) : 0,50 mm² : 39,7 Ω/km;
                                    0,75 mm² : 26,5 Ω/km;
                                      1,5 mm² : 12,3 Ω/km.
RE-Y(St)Y-PIMF   70° C - 
CU/PVC/ISCR/OSCR/PVC - Multi-pair, PVC insulated, individual and collective screened, PVC sheathed instrumentation cable 300/500 V

Standards

Design                    : BS 5308 Part 2 Type 1.

Conductor               : BS 6360.

Insulation                : BS 6746.

Outer sheath            : BS 7655.

Flame retardancy test : IEC 60332-1 & BS EN 60332-1.
 
RE-Y(St)Y-PIMF   70° C - 
CU/PVC/ISCR/OSCR/PVC - Multi-pair, PVC insulated, individual and collective screened, PVC sheathed instrumentation cable 300/500 V
 
Applications


These cables are used for transmission of analogue and digital signals in instrument and control systems at chemistry and petrochemistry industry 
plants, power plants, natural gas and petroleum plants, etc... .
Instrumentation cables are not allowed for direct connection to a low impedance 
source, e.g. public mains electricity supply.
These cables are not recommended for direct burial.
They are for indoor and oudoor installation, 
in dry and wet locations; on racks, trays, in conduits.

All Rights Reserved Halley Cables © 2006 - 2024