Construction
 
Conductor      : plain annealed copper wire, BS 6360
                      0,50 mm² and 1,0 mm² solid,
                      0,50 mm² flexible or
                      1,5 mm² stranded.

Insulation       : PE compound.

Core ident.     : black / blue.

PIMF constr.   : polyester tape above the pair, AL-PES tape
                      over tinned copper drain wire, 0,50 mm².

Lay-up           : PIMF laid up in layers of optimum pitch.

Separator       : polyester tape.

Screen           : AL-PES tape over tinned copper drain wire 0,50 mm².

Outer sheath  : PVC compound, flame retardant; TM1.

Sheath colour : RAL 9005, black.

More details

RE-2Y(St)Y-fl-PIMF
 70° C - CU/PE/ISCR/OSCR/PVC - Multi-pair, PE insulated, individual & collective screened, PVC sheathed instrumentation cable 300/500 V
 
Technical data and tests

Rated voltage (U°/U)           : 300/500 V.


Insulation thickness              : 0,50 mm² : 0,50 mm;  
                                            1,0 mm² : 0,60 mm;
                                          0,50 mm² : 0,60 mm;
                                          1,50 mm² : 0,60 mm.

Conductor class, BS 6360      : 0,50 mm² : Class 1;
                                            1,0 mm² : Class 1;
                                          0,50 mm² : Class 5;
                                            1,5 mm² : Class 2.

Conductor resistance (20° C) : 0,50 mm² : 36,8 Ω/km;
                                             1,0 mm² : 18,4 Ω/km;
                                           0,50 mm² : 39,7 Ω/km;
  
                                             1,5 mm² : 12,3 Ω/km.

Insulation resistance (20° C)  : min. 5000 MΩ/km.

Mutual capacitance (1 kHz)    : 0,50 mm² : max. 115 pF/m
                                             1,0 mm² : max. 115 pF/m
                                             1,5 mm² : max. 120 pF/m.

Capacitance unbalanced        : (1 kHz) : max. 250 pF/250 m

L/R (oran-ratio) (max)           : 0,50 mm² : 25 µH/Ω; 1,0 mm² : 25 µH/Ω;  1,5 mm² : 40 µH/Ω.

Test voltage                        : Urms core-core    : 1000 V;
                                           Urms core-screen : 1000 V.

Temperature range              : operation  : - 40° C ~ + 70° C;
                                         installation :   - 5° C ~ + 50° C.

Min. bending radius              : 6 x D.
 
RE-2Y(St)Y-fl-PIMF
 70° C - CU/PE/ISCR/OSCR/PVC - Multi-pair, PE insulated, individual & collective screened, PVC sheathed instrumentation cable 300/500 V
 
Standards
 

Design                     : BS 5308 Part 1 Type 1.

Conductor                : BS 6360.

Insulation                 : BS 6234 Type 03.

Outer sheath             : TM1, BS 7655.

Flame retardancy test  : IEC 60332-1 & BS EN 60332-1.
 
RE-2Y(St)Y-fl-PIMF
 70° C - CU/PE/ISCR/OSCR/PVC - Multi-pair, PE insulated, individual & collective screened, PVC sheathed instrumentation cable 300/500 V
 
Applications


These cables are used for transmission of analogue and digital signals in instrumentation and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc... .
Instrumentation cables are not allowed for direct connection to a low impedance sources, e.g. public mains electricity supply.
These cables are not recommended for direct burial.
They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.

All Rights Reserved Halley Cables © 2006 - 2024