RE-2Y(St)HSWAH & RE-2X(St)HSWAH
 - PE and XLPE insulated, LSZH sheathed instrumentation cables (300/500 V) Maximize

RE-2Y(St)HSWAH & RE-2X(St)HSWAH
 - PE and XLPE insulated, LSZH sheathed instrumentation cables (300/500 V)

RE-2Y(St)HSWAH & RE-2X(St)HSWAH instrumentation cables - Construction


Conductor            : plain annealed copper wire, BS 6360 0,50 mm²
                            and 1,0 mm² flexible, 0,50 mm²
                            and 0,75 mm² flexible or 1,5 mm² stranded.

Insulation (2Y)      : PE compound, BS 6234 TYPE 03 (RE-2Y...).

Insulation (2X)      : XLPE compound, GP 8, BS 7655 (RE-2X...).

Core identification : black / white / red (1-1-1, 2-2-2,…).

Separator            : polyester tape.

Screen                : AL-PES tape over tinned copper drain wire.

Bedding               : LSZH compound, Black.

Armour                : galvanized round steel wire, BS EN 10257-1.

Outer sheath        : LSZH compound, LST1, BS 7655;  
Sheath colour       : RAL 9005, black or RAL 5015, blue.

More details

RE-2Y(St)HSWAH & RE-2X(St)HSWAH instrumentation cables - Technical data and tests

Rated voltage (U°/U)            : 300/500 V.
Capacitance unbalanced         : (1 kHz) : max. 250 pF/250 m.

Standard                              : BS 5308 Part 1 Type 1.
Insulation resistance              : min. 5000 MΩ/km.

Flame retardancy test            : IEC 60332-1 & BS EN 60332-1.  
  
                                            IEC 60332-3 & BS EN 50266-2-4.
Smoke density test                : IEC 61034-2 & BS EN 61034-2.
Halogen-free properties test    : IEC60754-1/2 & BS EN 50267-2.
Test voltage                         : Urms core-core : 1000 V;
                                            Urms core-screen : 1000 V.          
Temperature range (2Y)        : operation  : - 40° C ~ + 70° C;   

                                            installation :   - 5° C ~ + 50° C.

Temperature range (2X)        : operation: - 40° C ~ + 90° C;    
                                            installation: - 5° C ~ + 50° C.
Min. bending radius               : 8 x D.
 
RE-2Y(St)HSWAH & RE-2X(St)HSWAH instrumentation cables - Applications
These cables are used for transmission of analogue and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc.
Instrumentation cables are not allowed for direct connection to a low impedance sources, e.g. public mains electricity supply.
In case of fire, these cables inhibit the propagation of the flames whereby the development of smoke is extremely low.
No corrosive gases are emitted in the event of fire.
With blue sheath it is suitable for intrinsically safe systems.
These cables are not recommended for direct burial.
They are for indoor and oudoor installation, in dry and wet locations; on racks, trays, in conduits.