RE-2Y(St)Y-fl-PIMF 70° C - CU/PE/ISCR/OSCR/PVC Maximize

RE-2Y(St)Y-fl-PIMF 70° C - CU/PE/ISCR/OSCR/PVC

RE-2Y(St)Y-fl-PIMF 70° C - CU/PE/ISCR/OSCR/PVC - PE insulated, PVC sheathed instrumentation cable 500 V
 
Construction

Conductor            : plain copper wire, stranded.

Insulation             : PE compound (RE-2Y...).
PIMF Construction : polyester tape above the pair, AL-PES tape over solid
                            tinned copper drain wire, 0,60 mm.
Separator             : polyester tape.
Screen                 : AL-PES tape over stranded tinned copper drain
                            wire 0,50 mm².

Outer sheath         : PVC compound, flame retardant.

Sheath colour       : RAL 9005, black or RAL 5015, blue.

*Please check the data sheet for detailed information.

More details

RE-2Y(St)Y-fl-PIMF 70° C - CU/PE/ISCR/OSCR/PVC - PE insulated, PVC sheathed instrumentation cable 500 V
 
Technical data and tests


Rated voltage                   : 500 V.
Test voltage                     : Urms core-core    : 2000 V;

                                       Urms core-screen : 2000 V.
Temperature range            : operation : - 30° C ~ + 70° C;
                                       installation : - 5° C ~ + 50° C.
Min. bending radius           : 7,5 x D.
Insulation resistance          : min. 5000 MΩ/km.

Mutual capacitance (1 kHz) : max. 100 pF/m.
 
RE-2Y(St)Y-fl-PIMF 70° C - CU/PE/ISCR/OSCR/PVC - PE insulated, PVC sheathed instrumentation cable 500 V

Technical data and tests


Conductor resistance   : 0,50 mm² : 36,0 Ω/km;
                               
  0,75 mm² : 24,5 Ω/km;

                                   1,0 mm² : 18,1 Ω/km;
                                   1,3 mm² : 13,9 Ω/km;

                                   1,5 mm² : 12,1 Ω/km.

L/R (ratio) (max)        : 0,50 mm² : 25 µH/Ω;
                                 0,75 mm² : 25 µH/Ω;

                                   1,0 mm² : 25 µH/Ω;

                                   1,3 mm² : 40 µH/Ω;
                                   1,5 mm² : 40 µH/Ω.

Mutual capacitance    : max 100 pF/m (1 kHz).

RE-2Y(St)Y-fl-PIMF 70° C - CU/PE/ISCR/OSCR/PVC - PE insulated, PVC sheathed instrumentation cable 500 V

Standards


Design               : DIN EN 50288-7.

Conductor          : IEC 60228 class 2, DIN EN 60228 class 2.

Insulation           : EN 50290-2-23.

Outer sheath       : EN 50290-2-22.

Flame retardancy : IEC 60332-1 & EN 60332-1.
 
RE-2Y(St)Y-fl-PIMF 70° C - CU/PE/ISCR/OSCR/PVC - PE insulated, PVC sheathed instrumentation cable 500 V
 
Applications

These cables are used for transmission of analogue and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc... .
Instrumentation cables are not allowed for direct connection to a low impedance source, e.g. public mains electricity supply.
With blue sheath it is suitable for intrinsically safe systems.
These cables are not recommended for direct burial.
They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.