RE-2Y(St)HSWAH-PIMF 70° C - CU/PE/ISCR/OSCR/LSZH/SWA/LSZH - PE insulated, armour, LSZH sheathed instrumentation cable 300/500 V
Technical data and tests
Rated voltage (Uo/U) : 300/500 V.
Test voltage : Urms core-core : 1000 V;
Urms core-screen : 1000 V.
Temperature range : operation : - 40° C ~ + 70° C;
installation : - 5° C ~ + 50° C.
Capacitance unbalanced : (1 kHz) : max. 250 pF/250 m.
Insulation resistance : min. 5000 MΩ/km.
Min. bending radius : 8 x D.
L/R (ratio) (max) : 0,50 mm² : 25 µH/Ω;
0,75 mm² : 25 µH/Ω;
1,0 mm² : 25 µH/Ω;
1,5 mm² : 40 µH/Ω.
RE-2Y(St)HSWAH-PIMF 70° C - CU/PE/ISCR/OSCR/LSZH/SWA/LSZH - PE insulated, armour, LSZH sheathed instrumentation cable 300/500 V
Technical data and tests
Insulation thickness : 0,50 mm² : 0,50 mm;
1,0 mm² : 0,60 mm;
0,50 mm² : 0,60 mm;
0,75 mm² : 0,60 mm;
1,50 mm² : 0,60 mm.
Conductor class, BS 6360 : 0,50 mm² : Class 1;
1,0 mm² : Class 1;
0,50 mm² : Class 5;
0,75 mm² : Class 5;
1,50 mm² : Class 2.
Conductor resistance : 0,50 mm² : 36,8 Ω/km;
1,0 mm² : 18,4 Ω/km;
0,50 mm² : 39,7 Ω/km;
0,75 mm² : 26,5 Ω/km;
1,50 mm² : 12,3 Ω/km.
Mutual capacitance (1 kHz) : ≤2 pairs all other pairs
0,50 mm² : max. 115 pF/m, max. 75 pF/m;
0,75 mm² : max. 115 pF/m, max. 75 pF/m;
1,0 mm² : max. 115 pF/m, max. 75 pF/m;
1,5 mm² : max. 120 pF/m, max. 85 pF/m.
RE-2Y(St)HSWAH-PIMF 70° C - CU/PE/ISCR/OSCR/LSZH/SWA/LSZH - PE insulated, armour, LSZH sheathed instrumentation cable 300/500 V Standards
Design : BS 5308 Part 1 Type 1.
Conductor : BS 6360.
Insulation : BS 6234 Type 03.
Armour : BS EN 10257-1.
Outer sheath : BS 7655.
Flame retardancy : IEC 60332-1 & BS EN 60332-1.
IEC 60332-3 & BS EN 50266-2-4.
Smoke density : IEC 61034-2 & BS EN 61034-2.
Halogen-free : IEC 60754-1/2 & BS EN 50267-2.
RE-2Y(St)HSWAH-PIMF 70° C - CU/PE/ISCR/OSCR/LSZH/SWA/LSZH - PE insulated, armour, LSZH sheathed instrumentation cable 300/500 V
Applications
These cables are used for transmission of analogue and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroluem plants, etc... .
Instrumentation cables are not allowed for direct connection to a low impedance source, e.g. public mains electricity supply.
In case of fire, these cables inhibit the propagation of the flames whereby the development of smoke is extremely low.
No corrosive gases are emitted in the event of fire. With blue sheath it is suitable for intrinsically safe systems.
The armour above the inner sheath protects the cable from mechanical shocks.
These cables are recommended for direct burial.
They are for indoor and oudoor installation, in dry and wet locations; on racks, trays, in conduits.