Categories

RE-Y(St)Y-fl-MP 70° C
 - CU/PVC/OSCR/PVC Maximize

RE-Y(St)Y-fl-MP 70° C
 - CU/PVC/OSCR/PVC

RE-Y(St)Y-fl-MP 70° C
 - CU/PVC/OSCR/PVC - Single & multi-pair, PVC insulated, collective screened, PVC sheathed instrumentation cable 300/500 V
 
Construction

Conductor            : plain annealed copper wire, BS 6360 0,50 mm² and
                             0,75 mm² flexible, or 1,5 mm² stranded.

Insulation             : PVC compound, TI1, BS 6746.

Core identification : according to BS 5308 Part 2 colour coded.

Pair                     : two conductors twisted to a pair.

Lay-up                 : pairs laid up in layers of optimum pitch.

Separator             : polyester tape.

Screen                 : AL-PES tape over tinned copper drain wire 0,50 mm².

Outer sheath        : PVC compound, flame retardant; TM1, BS 7655.

Sheath colour       : RAL 9005, black.

More details

RE-Y(St)Y-fl-MP 70° C
 - CU/PVC/OSCR/PVC - Single & multi-pair, PVC insulated, collective screened, PVC sheathed instrumentation cable 300/500 V
 
Technical data and tests

Rated voltage (U°/U)           : 300/500 V.

Test voltage                       :  Urms core-core    : 1000 V;
                                          Urms core-screen : 1000 V.

Insulation resistance (20° C) :  min. 25 MΩ/km.

Mutual capacitance (1 kHz)   :  max. 250 pF/m.

Capacitance unbalanced       : (1 kHz) : max. 450 pF/250 m.

Temperature range              :  operation : - 40° C ~ + 70° C;
                                          ınstallation : - 5° C ~ + 50° C.

Min. bending radius            :  6 x D.
RE-Y(St)Y-fl-MP 70° C
 - CU/PVC/OSCR/PVC - Single & multi-pair, PVC insulated, collective screened, PVC sheathed instrumentation cable 300/500 V
Technical data and tests

Insulation thickness             : 0,50 mm² : 0,60 mm;
                                         0,75 mm² : 0,60 mm;
                                         1,50 mm² : 0,60 mm.

Conductor class, BS 6360     : 0,50 mm² : Class 5;
                                          0,75 mm² : Class 5;
                                            1,5 mm² : Class 2.

Conductor resistance (20° C) : 0,50 mm² : 39,7 Ω/km;
                                          0,75 mm² : 26,5 Ω/km;
                                            1,5 mm² : 12,3 Ω/km.

L/R (oran-ratio) (max)      : 0,50 mm² : 25 µH/Ω;
                                      0,75 mm² : 25 µH/Ω;
                                        1,5 mm² : 40 µH/Ω.
RE-Y(St)Y-fl-MP 70° C
 - CU/PVC/OSCR/PVC - Single & multi-pair, PVC insulated, collective screened, PVC sheathed instrumentation cable 300/500 V
Standards

Design               : BS 5308 Part 2 Type 1.

Conductor          : BS 6360.

Insulation           : BS 6746.

Outer sheath        : BS 7655.

Flame retardancy  : IEC 60332-1 & BS EN 60332-1.
RE-Y(St)Y-fl-MP 70° C
 - CU/PVC/OSCR/PVC - Single & multi-pair, PVC insulated, collective screened, PVC sheathed instrumentation cable 300/500 V
 
Applications


These cables are used for transmission of analogue and digital signals in instrument and control systems at chemistry and petrochemistry industry 
plants, power plants, natural gas and petroleum plants, etc... .
Instrumentation cables are not allowed for direct connection to a low impedance 
source, e.g. public mains electricity supply.
These cables are not recommended for direct burial.
They are for indoor and outdoor installation, 
in dry and wet locations; on racks, trays, in conduits.

All Rights Reserved Halley Cables © 2006 - 2024