RE-2YCY-fl
 70° C - CU/PE/OSCR/PVC Maximize

RE-2YCY-fl
 70° C - CU/PE/OSCR/PVC

RE-2YCY-fl
 70° C - CU/PE/OSCR/PVC - PE insulated, collective screened, 
PVC sheathed instrumentation cable 300 V
 
Construction
 

Conductor            : plain copper wire, stranded.
Insulation             : PE compound, EN 50290-2-23.
Core identification : black / white cores numbered 1-1, 2-2,…
Upon request        : colour coded according to IEC 60189-2.

Pair                      : two conductors twisted to a pair.
Lay-up                 : pairs laid up in layers of optimum pitch.
Separator             : polyester tape.
Screen                  : braid of tinned Cu wires, 85% coverage.
Outer sheath         : PVC comp., flame retardant; EN 50290-2-22.
Sheath colour        : RAL 9005, black or RAL 5015, blue.

More details

RE-2YCY-fl
 70° C - CU/PE/OSCR/PVC - PE insulated, collective screened, 
PVC sheathed instrumentation cable 300V
 
Technical data and tests

Rated voltage               : 300V.
Insulation resistance     : min. 5000 MΩ/km.
Capacitance unbalance  : (1 kHz) : max. 500 pF/500 m.
Test voltage                 : Urms core-core    : 1500 V;
                                    Urms core-screen : 1500 V.
Temperature range       : operation   : - 30° C ~ + 70° C;
                                  installation :   - 5° C ~ + 50° C.
Min. bending radius       : 7,5 x D.
 
RE-2YCY-fl
 70° C - CU/PE/OSCR/PVC - PE insulated, collective screened, 
PVC sheathed instrumentation cable 300V

Standards
 

Design               : DIN EN 50288-7.

Conductor          : IEC 60228 class 2, DIN EN 60228 class 2.

Insulation           : EN 50290-2-23.

Outer sheath       : EN 50290-2-22.

Flame retardancy : IEC 60332-1 & EN 60332-1.
 
RE-2YCY-fl
 70° C - CU/PE/OSCR/PVC - PE insulated, collective screened, 
PVC sheathed instrumentation cable 300V
 
Applications


These cables are used for transmission of analogue and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc... .
Instrumentation cables are not allowed for direct connection to a low impedance source, e.g. public mains electricity supply.
With blue sheath it is suitable for intrinsically safe systems.
These cables are not recommended for direct burial.
They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits. 