Categories

RE-2YCYSWAY-fl-PIMF 70° C
 - CU/PE/ISCR/OSCR/PVC/SWA/PVC Maximize

RE-2YCYSWAY-fl-PIMF 70° C
 - CU/PE/ISCR/OSCR/PVC/SWA/PVC

RE-2YCYSWAY-fl-PIMF 70° C
 - CU/PE/ISCR/OSCR/PVC/SWA/PVC - PE insulated, individual & collective screened, 
armoured PVC sheathed cable 300 V
 
Construction


Conductor             : plain copper wire, stranded; IEC 60228 Sinif 2,
                              TS/DIN EN 60228 Sinif 2.
Insulation             : PE compound, EN 50290-2-23.

PIMF Construction : polyester tape above the pair. 
Separator             : polyester tape.
Screen                 : braid of tinned Cu wires, 85% coverage.
Inner sheath         : PVC compound, EN 50290-2-22.
Armour                : galvanized round steel wire, EN 10257-1.
Outer sheath        : PVC compound, flame retardant; EN 50290-2-22.
Sheath colour       : RAL 9005, black or RAL 5015, blue.

More details

RE-2YCYSWAY-fl-PIMF 70° C
 - CU/PE/ISCR/OSCR/PVC/SWA/PVC - PE insulated, individual & collective screened, 
armoured PVC sheathed cable 300 V
 
Technical data and tests

Rated voltage              : 300 V.
Test voltage                : Urms core-core    : 1500 V;
                                  Urms core-screen : 1500 V.    
Temperature range      : operation : - 30° C ~ + 70° C;  
                                  installation : - 5° C ~ + 50° C.  
Min. bending radius     : 10 x D.
Insulation resistance    : min. 5000 MΩ/km.
Capacitance unbalance : (1 kHz) : max. 500 pF/500 m.
 
RE-2YCYSWAY-fl-PIMF 70° C
 - CU/PE/ISCR/OSCR/PVC/SWA/PVC - PE insulated, individual & collective screened, 
armoured PVC sheathed cable 300 V

Standards


Design               : DIN EN 50288-7.

Conductor          : IEC 60228 class 2, DIN EN 60228 class 2.

Insulation           : EN 50290-2-23.

Armour              : EN 10257-1.

Outer sheath       : EN 50290-2-22.

Flame retardancy : IEC 60332-1 & EN 60332-1.
 
RE-2YCYSWAY-fl-PIMF 70° C
 - CU/PE/ISCR/OSCR/PVC/SWA/PVC - PE insulated, individual & collective screened, 
armoured PVC sheathed cable 300 V
 
Applications

These cables are used for transmission of analogue and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroluem plants, etc... .
Instrumentation cables are not allowed for direct connection to a low impedance source, e.g. public mains electricity supply.
With blue sheath it is suitable for intrinsically safe systems.
The armour above the inner sheath protects the cable from mechanical shocks.
These cables are recommended for direct burial.
They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.