Categories

RE-2Y(St)YSWAY-fl 70° C - CU/PE/OSCR/PVC/SWA/PVC Maximize

RE-2Y(St)YSWAY-fl 70° C - CU/PE/OSCR/PVC/SWA/PVC

RE-2Y(St)YSWAY-fl 70° C - CU/PE/OSCR/PVC/SWA/PVC - PE insulated armoured, PVC sheathed instrumentation cable 300 V
 
Construction

Conductor           : plain copper wire, stranded.

Insulation            : PE compound, (RE-2Y….).

Core identification : black / white / red cores are numbered (1-1-1, 2-2-2,…).
Upon request        : colour coded according to IEC60189-2.
     

Lay-up                 : triples laid up in layers of optimum pitch.

Separator             : polyester tape.

Screen                 : AL-PES tape over tinned copper drain wire 0,50 mm².

Inner sheath         : PVC compound, flame retardant.

Armour                : galvanized round steel wire.

Outer sheath         : PVC compound, flame retardant.

Sheath colour       : RAL 9005, black or RAL 5015, blue.

More details

RE-2Y(St)YSWAY-fl 70° C - CU/PE/OSCR/PVC/SWA/PVC - PE insulated armoured, PVC sheathed instrumentation cable 300 V
 
Technical data and tests

Rated voltage                     : 300 V.

Test voltage                       : Urms core-core    : 1500 V;

                                         Urms core-screen : 1500 V.

Temperature range              : operation   : - 30° C ~ + 70° C;
                                       
  installation :   - 5° C ~ + 50° C.

Min. bending radius            : 10 x D.

Insulation resistance           : min. 5000 MΩ/km.
Insulation thickness            : 0,50 mm² : 0,40 mm;
                                        0,75 mm² : 0,40 mm;

                                          1,0 mm² : 0,40 mm;

                                          1,3 mm² : 0,45 mm;
                                          1,5 mm² : 0,45 mm.

Conductor resistance          : 0,50 mm² : 36,7 Ω/km;

                                        0,75 mm² : 25,0 Ω/km;

                                          1,0 mm² : 18,5 Ω/km;
                                          1,3 mm² : 14,2 Ω/km;

                                          1,5 mm² : 12,3 Ω/km.

L/R (ratio) (max)               : 0,50 mm² : 25 µH/Ω;
                                        0,75 mm² : 25 µH/Ω;
                                      
    1,0 mm² : 25 µH/Ω;

                                          1,3 mm² : 40 µH/Ω;
                                          1,5 mm² : 40 µH/Ω.

Mutual capacitance (1 kHz) :            ≤ 4 pairs                   all other pairs

                                        0,50 mm² : max. 115 pF/m,   max. 90 pF/m;
                                      
  0,75 mm² : max. 115 pF/m,   max. 90 pF/m;

                                          1,0 mm² : max. 115 pF/m,   max. 90 pF/m;

                                          1,3 mm² : max. 120 pF/m,  max. 105 pF/m;

                                          1,5 mm² : max. 120 pF/m,  max. 105 pF/m.
 
RE-2Y(St)YSWAY-fl 70° C - CU/PE/OSCR/PVC/SWA/PVC - PE insulated armoured, PVC sheathed instrumentation cable 300 V
 
Standards


Design                 : DIN EN 50288-7.

Conductor            : IEC 60228 class 2, DIN EN 60228 class 2.

Insulation             : EN 50290-2-23.

Armour                : EN 10257-1.

Inner/outer sheath : EN 50290-2-22.

Flame retardancy   : IEC 60332-1 & EN 60332-1.
 
RE-2Y(St)YSWAY-fl 70° C - CU/PE/OSCR/PVC/SWA/PVC - PE insulated armoured, PVC sheathed instrumentation cable 300 V
 
Applications


These cables are used for transmission of analogue and digital signals in instrumentation and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc... .
Instrumentation cables are not allowed for direct connection to a low impedance source, e.g. public mains electricity supply.
With blue sheath it is suitable for intrinsically safe systems.
The armour above the inner sheath protects the cable from mechanical shocks.
These cables are recommended for direct burial.
They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.