RE-2Y(St)Y-fl MP  70° C - CU/PE/OSCR/PVC Maximize

RE-2Y(St)Y-fl MP 70° C - CU/PE/OSCR/PVC

RE-2Y(St)Y-fl MP  70° C - CU/PE/OSCR/PVC - PE insulated, collective screened, PVC sheathed instrumentation cable 500 V
 
Construction

Conductor            : plain copper wire, stranded.

Insulation             : PE compound (RE-2Y...).

Core identification : black /white cores numbered 1-1, 2-2,…
Upon request        : colour coded according to IEC 60189-2.

Pair                     : two conductors twisted to a pair.
Lay-up                 : pairs laid up in layers of optimum pitch.
Separator             : polyester tape.
Screen                 : AL-PES tape over stranded tinned copper drain
                            wire 0,50 mm².

Outer sheath         : PVC compound, flame retardant.

Sheath colour       : RAL 9005, black or RAL 5015, blue.

More details

RE-2Y(St)Y-fl MP  70° C - CU/PE/OSCR/PVC - PE insulated, collective screened, PVC sheathed instrumentation cable 500 V
 
Technical data and tests

Rated voltage          : 500 V.

Test voltage            : Urms core-core   : 2000 V;
                            
  Urms core-screen : 2000 V.

Temperature range   : operation   : - 30° C ~ + 70° C;

                              installation :   - 5° C ~ + 50° C.

Min. bending radius : 7.5 x D.

Insulation resistance : min. 5000 MΩ/km.
 
RE-2Y(St)Y-fl MP  70° C - CU/PE/OSCR/PVC - PE insulated, collective screened, PVC sheathed instrumentation cable 500 V

Technical data and tests

Conductor resistance : 0,50 mm² : 36,7 Ω/km;

                               0,75 mm² : 25,0 Ω/km;

                                 1,0 mm² : 18,5 Ω/km;
                                 1,3 mm² : 14,2 Ω/km;
                           
      1,5 mm² : 12,3 Ω/km.

L/R (ratio) (max)       : 0,50 mm² : 25 µH/Ω;
                                0,75 mm² : 25 µH/Ω;

                                  1,0 mm² : 25 µH/Ω;

                                  1,3 mm² : 40 µH/Ω;
                                  1,5 mm² : 40 µH/Ω.

Insulation thickness    : 0,50 mm² : 0,40 mm;
                                 0,75 mm² : 0,40 mm;

                                   1,0 mm² : 0,40 mm;

                                   1,3 mm² : 0,45 mm;
                                   1,5 mm² : 0,45 mm.

Mutual capacitance  :        ≤ 4 pairs                       all other pairs

                               0,50 mm² : max. 100 pF/m,  max. 65 pF/m;
                               0,75 mm² : max. 100 pF/m,  max. 65 pF/m;
                                 1,0 mm² : max. 100 pF/m,  max. 65 pF/m;
                                 1,3 mm² : max. 100 pF/m,  max. 75 pF/m;
                                 1,5 mm² : max. 100 pF/m,  max. 75 pF/m.

RE-2Y(St)Y-fl MP  70° C - CU/PE/OSCR/PVC - PE insulated, collective screened, PVC sheathed instrumentation cable 500 V

Standards

Design               : DIN EN 50288-7.

Conductor          : IEC 60228 class 2, DIN EN 60228 class 2.

Insulation           : EN 50290-2-23.

Outer sheath       : EN 50290-2-22.

Flame retardancy : IEC 60332-1 & EN 60332-1.
 
RE-2Y(St)Y-fl MP  70° C - CU/PE/OSCR/PVC - PE insulated, collective screened, PVC sheathed instrumentation cable 500 V
 
Applications


These cables are used for transmission of analogue and digital signals in instrumentation and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc... .
Instrumentation cables are not allowed for direct connection to a low impedance source, e.g. public mains electricity supply.
With blue sheath it is suitable for intrinsically safe systems.
These cables are not recommended for direct burial.
They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.