Categories

RE-2Y(St)2YSWAY-fl 70° C - CU/PE/OSCR/PE/SWA/PVC Maximize

RE-2Y(St)2YSWAY-fl 70° C - CU/PE/OSCR/PE/SWA/PVC

RE-2Y(St)2YSWAY-fl 70° C - CU/PE/OSCR/PE/SWA/PVC - PE insulated, collective screened, armoured, PVC sheathed instrumentation cable 300/500 V
 
Construction

Conductor            : plain annealed copper wire, BS 6360.
Insulation             : PE compound, BS 6234 Type03.
Core identification : black / white / red cores are numbered (1-1-1, 2-2-2,…).
Lay-up                 : triples laid up in layers of optimum pitch.
Separator             : polyester tape.
Screen                 : AL-PES tape over tinned copper drain wire 0,50 mm².
Bedding               : PE compound, BS 6234 Type 03, black.
Armour                : galvanized round steel wire, BS EN 10257-1.
Outer sheath        : PVC compound, flame retardant; TM1, BS 7655.
Sheath colour       : RAL 9005, black or RAL 5015, blue.

More details

RE-2Y(St)2YSWAY-fl 70° C - CU/PE/OSCR/PE/SWA/PVC - PE insulated, collective screened, armoured, PVC sheathed instrumentation cable 300/500 V
 
Technical data and tests

Rated voltage (U°/U)            : 300/500 V.
Insulation resistance (20° C) : min. 5000 MΩ / km.
Capacitance unbalanced       : (1 kHz) : max. 250 pF/250 m.
Test voltage                        : Urms core-core    : 1000 V;  
                                           Urms core-screen : 1000 V.
Temperature range              : operation : - 40° C ~ + 70° C;
                                           installation : - 5° C ~ + 50° C.
Min. bending radius             : 8 x D.
 
RE-2Y(St)2YSWAY-fl 70° C - CU/PE/OSCR/PE/SWA/PVC - PE insulated, collective screened, armoured, PVC sheathed instrumentation cable 300/500 V

Standards
 
Design                    : BS 5308 Part 1 Type 2.
Conductor               : BS 6360.
Insulation & Bedding : BS 6234 Type 03.
Armour                    : BS EN 10257-1. 
Outer sheath             : TM1, BS 7655.
Flame retardancy test : IEC 60332-1 & BS EN 60332-1.

RE-2Y(St)2YSWAY-fl 70° C - CU/PE/OSCR/PE/SWA/PVC - PE insulated, collective screened, armoured, PVC sheathed instrumentation cable 300/500 V
 
Applications

These cables are used for transmission of analogue and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc.
Instrumentation cables are not allowed for direct connection to a low impedance source, e.g. public mains electricity supply.
With blue sheath it is suitable for intrinsically safe systems.
The armour above the inner sheath protects the cable from mechanical shocks.
These cables are recommended for direct burial.
They are for indoor and oudoor installation, in dry and wet locations; on racks, trays, in conduits.

All Rights Reserved Halley Cables © 2006 - 2024