Categories

RE-2Y(St)2YSWAY-fl-MP 70° C - CU/PE/OSCR/PE/SWA/PVC Maximize

RE-2Y(St)2YSWAY-fl-MP 70° C - CU/PE/OSCR/PE/SWA/PVC

RE-2Y(St)2YSWAY-fl-MP 70° C - CU/PE/OSCR/PE/SWA/PVC - PE insulated, screened, armoured, 
PVC sheathed instrumentation cable 300/500 V
 
Construction

Conductor            : plain annealed copper wire, BS 6360.

Insulation             : PE compound, BS 6234 Type 03.

Core identification : according to BS 5308 Part 1 colour coded.

Pair                     : two conductors twisted to a pair.

Separator             : polyester tape.

Screen                 : AL-PES tape over tinned copper drain wire.

Bedding               : PE compound, BS 6234 Type 03, Black.

Armour                : galvanized round steel wire, BS EN 10257-1.

Outer sheath        : PVC compound, flame retardant; TM1, BS 7655.

Sheath colour       : RAL 9005, black.

More details

RE-2Y(St)2YSWAY-fl-MP 70° C - CU/PE/OSCR/PE/SWA/PVC - PE insulated, screened, armoured, 
PVC sheathed instrumentation cable 300/500 V
 
Technical data and tests

Insulation resistance       : min. 5000 MΩ/km.
Test voltage                  : Urms core-core    : 1000 V;
  
                                     Urms core-screen : 1000 V.

Rated voltage (U°/U)      : 300/500V.

Temperature range         : operation  : - 40° C ~ + 70° C;

                                    installation :  - 5 °C ~ + 50° C.

Min. bending radius       : 8 x D.

Capacitance unbalanced : (1 kHz) : max. 250 pF/250 m.
 
RE-2Y(St)2YSWAY-fl-MP 70° C - CU/PE/OSCR/PE/SWA/PVC - PE insulated, screened, armoured, 
PVC sheathed instrumentation cable 300/500 V
 
Standards

Design                   : BS 5308 Part 1 Type 2.

Insulation               : BS 6234 Type 03.

Core identification    : BS 5308 Part 1 colour coded.

Bedding                  : BS 6234 Type 03.

Armour                   : BS EN 10257-1.

Outer sheath            : TM1, BS 7655.

Flame retardancy test : IEC 60332-1 & BS EN 60332-1.
 
RE-2Y(St)2YSWAY-fl-MP 70° C - CU/PE/OSCR/PE/SWA/PVC - PE insulated, screened, armoured, 
PVC sheathed instrumentation cable 300/500 V
 
Applications


These cables are used for transmission of analogue and digital signals in instrument and control systems at chemistry and petrochemistry industry 
plants, power plants, natural gas and petroleum plants, etc.
Instrumentation cables are not allowed for direct connection to a low impedance source, e.g. public mains electricity supply.
The armour above the inner sheath protects the cable from mechanical shocks.
These cables are recommended for direct burial.
They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.

All Rights Reserved Halley Cables © 2006 - 2024