RE-2Y(St)2YSWAY-fl-PIMF 70° C - CU/PE/ISCR/OCSR/PE/SWA/PVC Maximize

RE-2Y(St)2YSWAY-fl-PIMF 70° C - CU/PE/ISCR/OCSR/PE/SWA/PVC

RE-2Y(St)2YSWAY-fl-PIMF 70° C - CU/PE/ISCR/OCSR/PE/SWA/PVC - Multi-pair, PE insulated, screened, armoured, PVC sheathed instrumentation cable 300/500 V
 
Construction


Conductor            : plain annealed copper wire, BS 6360

Insulation             : PE compound, BS 6234 Type 03.
PIMF construction : polyester tape above the pair, AL-PES tape over
                             tinned copper drain wire.
Separator             : polyester tape.

Screen                 : AL-PES tape over tinned copper drain wire 0,50 mm².

Bedding               : PE compound, BS 6234 Type 03, Black.

Armour                : galvanized round steel wire, BS EN 10257-1.

Outer sheath        : PVC compound, flame retardant; TM1, BS 7655.

Sheath colour       : RAL 9005, black.

More details

RE-2Y(St)2YSWAY-fl-PIMF 70° C - CU/PE/ISCR/OCSR/PE/SWA/PVC - Multi-pair, PE insulated, screened, armoured, PVC sheathed instrumentation cable 300/500 V
 
Technical data and tests


Rated voltage (U°/U)            : 300/500 V.

Insulation resistance (20° C)   : min. 5000 MΩ/km.
Capacitance unbalanced         : (1 kHz) : max. 250 pF/250 m.
Test voltage                         : Urms core-core : 1000 V;  
                                           Urms core-screen : 1000 V.

Temperature range               : operation  : - 40° C ~ + 70° C;
                                           installation : - 5° C ~ + 50° C.

Min. bending radius              : 8 x D.

 
RE-2Y(St)2YSWAY-fl-PIMF 70° C - CU/PE/ISCR/OCSR/PE/SWA/PVC - Multi-pair, PE insulated, screened, armoured, PVC sheathed instrumentation cable 300/500 V
 
Standards

Design              : BS 5308 Part 1 Type 2.

Conductor         : BS 6360.

Insulation          : BS 6234 Type 03.

Armour              : BS EN 10257-1.

Bedding             : BS 6234 Type 3.

Outer sheath       : BS 7655.

Flame retardancy : IEC 60332-1 & BS EN 60332-1. 

                          IEC 60332-3 & BS EN 50266-2-4.

Smoke density     : IEC 61034-2 & BS EN 61034-2.

Halogen-free       : IEC 60754-1/2 & BS EN 50267-2.
 
RE-2Y(St)2YSWAY-fl-PIMF 70° C - CU/PE/ISCR/OCSR/PE/SWA/PVC - Multi-pair, PE insulated, screened, armoured, PVC sheathed instrumentation cable 300/500 V
 
Applications

These cables are used for transmission of analogue and digital signals in instrumentation and control systems at chemistry and petrochemistry industry 
plants, power plants, natural gas and petroleum plants, etc.
Instrumentation cables are not allowed for direct connection to a low impedance 
source e.g. public mains electricity supply.
The armour above the inner sheath protects the cable from mechanical shocks.
These cables are 
recommended for direct burial.
They are for indoor and oudoor installation, in dry and wet locations; on racks, trays, in conduits.