 Maximize

RE-2Y(St)HSWAH MP 70° C - CU/PE/OSCR/LSZH/SWA/LSZH


RE-2Y(St)HSWAH MP 70° C - CU/PE/OSCR/LSZH/SWA/LSZH
 - PE insulated, 
screened, armoured, LSZH sheathed instrumentation cable 300/500 V
 
Construction

Conductor             : plain annealed copper wire, BS 6360.

Insulation              : PE compound.
Core identification  : according to BS 5308 Part 1 colour coded.

Separator              : polyester tape.

Screen                  : AL-PES tape over tinned copper drain wire 0,50 mm².

Bedding                : LSZH compound, black.

Armour                 : galvanized round steel wire.
Outer sheath         : LSZH compound.
LSZH                    : Low Smoke Zero Halogen.

Sheath colour        : RAL 9005, black or RAL 5015, blue.

More details

RE-2Y(St)HSWAH MP 70° C - CU/PE/OSCR/LSZH/SWA/LSZH
 - PE insulated, 
screened, armoured, LSZH sheathed instrumentation cable 300/500 V
 
Technical data and tests

Rated voltage (Uo/U)     : 300/500 V.

Test voltage                  : Urms core-core    : 1000 V;
                                    
  Urms core-screen : 1000 V.

Temperature range        : operation : - 40° C ~ + 70° C;
                                    
  installation : - 5° C ~ + 50° C.

Capacitance unbalanced  : (1 kHz) : max. 250 pF/250 m.

Insulation resistance       : min. 5000 MΩ/km.

Min. bending radius        : 8 x D.

L/R (ratio) (max)           : 0,50 mm² : 25 µH/Ω;
                                    
  0,75 mm² : 25 µH/Ω;

                                        1,0 mm² : 25 µH/Ω;

                                        1,5 mm² : 40 µH/Ω.
 
RE-2Y(St)HSWAH MP 70° C - CU/PE/OSCR/LSZH/SWA/LSZH
 - PE insulated, 
screened, armoured, LSZH sheathed instrumentation cable 300/500 V
Technical data and tests


Insulation thickness          : 0,50 mm² : 0,50 mm;
                                          1,0 mm² : 0,60 mm;

                                         0,50 mm² : 0,60 mm;
                                         0,75 mm² : 0,60 mm;
                                         1,50 mm² : 0,60 mm.

Conductor class, BS 6360   : 0,50 mm² : Class 1;

                                           1,0 mm² : Class 1;

                                         0,50 mm² : Class 5;
                                         0,75 mm² : Class 5;
                                         1,50 mm² : Class 2.

Conductor resistance         : 0,50 mm² : 36,8 Ω/km;

                                           1,0 mm² : 18,4 Ω/km;
                                         0,50 mm² : 39,7 Ω/km;
                                         0,75 mm² : 26,5 Ω/km;
                                         1,50 mm² : 12,3 Ω/km.
 
Mutual capacitance (1 kHz) :      ≤2 pairs                  all other pairs
                                 0,50  mm² : max. 115 pF/m,  max. 75 pF/m;
                                 0,75  mm² : max. 115 pF/m,  max. 75 pF/m;
                                    1,0 mm² : max. 115 pF/m,  max. 75 pF/m;
                          
          1,5 mm² : max. 120 pF/m,  max. 85 pF/m.
 
RE-2Y(St)HSWAH MP 70° C - CU/PE/OSCR/LSZH/SWA/LSZH
 - PE insulated, 
screened, armoured, LSZH sheathed instrumentation cable 300/500 V
 
Standards
 
Design                 : BS 5308 Part 1 Type 1.

Conductor            : BS 6360.

Insulation             : BS 6234 Type 03.

Armour                : BS EN 10257-1.
Outer sheath        : BS 7655.

Flame retardancy : IEC 60332-1 & BS EN 60332-1.
                          
   IEC 60332-3 & BS EN 50266-2-4.

Smoke density      : IEC 61034-2 & BS EN 61034-2.

Halogen-free        : IEC 60754-1/2 & BS EN 50267-2.
 
RE-2Y(St)HSWAH MP 70° C - CU/PE/OSCR/LSZH/SWA/LSZH
 - PE insulated, 
screened, armoured, LSZH sheathed instrumentation cable 300/500 V
 
Applications

These cables are used for transmission of analogue and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc.
Instrumentation cables are not allowed for direct connection to a low impedance source, e.g. public mains electricity supply.
In case of fire, these cables inhibit the propagation of the flames whereby the development of smoke is extremely low.
No corrosive gases are emitted in the event of fire.
With blue sheath it is suitable for intrinsically safe systems.
These cables are not recommended for direct burial.
They are for indoor and oudoor installation, in dry and wet locations; on racks, trays, in conduits.