RE-2Y(St)YQY-fl-TIMF 70° C - CU/PE/ISCR/OSCR/PVC/SWB/PVC Maximize

RE-2Y(St)YQY-fl-TIMF 70° C - CU/PE/ISCR/OSCR/PVC/SWB/PVC

RE-2Y(St)YQY-fl-TIMF 70° C - CU/PE/ISCR/OSCR/PVC/SWB/PVC - PE insulated, screened, 
steel wire braided, PVC sheathed instrumentation cable 300 V
 
Construction
 

Conductor             : plain copper wire, stranded.
Insulation             : PE compound.
Core identification : black / white / red.
TIMF Construction : polyester tape above the triple, AL-PES tape over
                           solid tinned copper drain wire, 0,60 mm.
Separator             : polyester tape.
Screen                 : AL-PES tape over stranded tinned copper drain wire.
Inner sheath        : PVC compound.
Sheath colour       : RAL 9005, black or RAL 5015, blue.
Armour                : braid of galvanized steel wires, aprox. 85% coverage.
Outer sheath        : PVC compound, flame retardant.

More details

RE-2Y(St)YQY-fl-TIMF 70° C - CU/PE/ISCR/OSCR/PVC/SWB/PVC - PE insulated, screened, 
steel wire braided, PVC sheathed instrumentation cable 300 V
 
Technical data and tests


Rated voltage          : 300 V.

Test voltage            : Urms core-core    : 1500 V;
                              Urms core-screen : 1500 V.

Temperature range   : operation    : - 30° C ~ + 70° C;

                              installation  :   - 5° C ~ + 50° C.

Insulation resistance : min. 5000 MΩ/km.
Mutual capacitance  : max. 120 pF/m.

Min. bending radius : 10 x D.m.
 
RE-2Y(St)YQY-fl-TIMF 70° C - CU/PE/ISCR/OSCR/PVC/SWB/PVC - PE insulated, screened, 
steel wire braided, PVC sheathed instrumentation cable 300 V

Technical data and tests
 

Insulation thickness  : 0,50 mm² : 0,40 mm;
                              0,75 mm² : 0,40 mm;
                                1,0 mm² : 0,40 mm;
                                1,3 mm² : 0,45 mm;
                                1,5 mm² : 0,45 mm.
Conductor resistance : 0,50 mm² : 36,7 Ω/km;
                               0,75 mm² : 25,0 Ω/km;
                                 1,0 mm² : 18,5 Ω/km;
                                 1,3 mm² : 14,2 Ω/km;
                                 1,5 mm² : 12,3 Ω/km.
L / R (ratio) (max.)  : 0,50 mm² : 25 µH/Ω;
                              0,75 mm² : 25 µH/Ω;
                                1,0 mm² : 25 µH/Ω;

                                1,3 mm² : 40 µH/Ω;
                                1,5 mm² : 40 µH/Ω.
 
RE-2Y(St)YQY-fl-TIMF 70° C - CU/PE/ISCR/OSCR/PVC/SWB/PVC - PE insulated, screened, 
steel wire braided, PVC sheathed instrumentation cable 300 V
 
Standards
 
Design              : DIN EN 50288-7.

Conductor         : IEC 60228 class 2, DIN EN 60228 class 2

Inner sheath      : EN 50290-2-22.

Outer sheath      : EN 50290-2-22.

Flame retardance : IEC 60332-1 & EN 60332-1.
 
RE-2Y(St)YQY-fl-TIMF 70° C - CU/PE/ISCR/OSCR/PVC/SWB/PVC - PE insulated, screened, 
steel wire braided, PVC sheathed instrumentation cable 300 V
 
Applications


These cables are used for transmission of analogue and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc... .
Instrumentation cables are not allowed for direct connection to a low impedance source, e.g. public mains electricity supply.
With blue sheath it is suitable for intrinsically safe systems.
The armour above the sheath, steel wire braid serves as protection against mechanical traverse loads and act as a magnetic screen against interference.
The galvanised steel wires are free of corrosion and oxidation.
They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.