RE-2Y(St)YQY-fl MP 70° C - CU/PE/OSCR/PVC/SWB/PVC Maximize

RE-2Y(St)YQY-fl MP 70° C - CU/PE/OSCR/PVC/SWB/PVC

RE-2Y(St)YQY-fl MP 70° C - CU/PE/OSCR/PVC/SWB/PVC - PE insulated, collective screened, steel wire braided, PVC sheathed instrumentation cable 300 V
 
Construction

Conductor            : plain copper wire, stranded IEC 60228 Sinif 2,
                             TS/DIN EN 60228 Sinif 2.
Insulation             : PE compound, EN 50290-2-23.
Core identification : black / white cores numbered 1-1, 2-2,...
Separator             : polyester tape.
Screen                 : AL-PES tape over stranded tinned copper drain wire.
Inner sheath        : PVC compound, EN 50290-2-22
Armour                : braid of galvanized steel wires, aprox. 85% coverage.
Outer sheath        : PVC compound, flame retardant; EN 50290-2-22.
Sheath colour       : RAL 9005, black or RAL 5015, blue.

More details

RE-2Y(St)YQY-fl MP 70° C - CU/PE/OSCR/PVC/SWB/PVC - PE insulated, collective screened, steel wire braided, PVC sheathed instrumentation cable 300 V
 
Technical data and tests

Rated voltage             : 300 V.

Test voltage               : Urms core-core    : 1500 V;

                                 Urms core-screen : 1500 V.

Temperature range      : operation : - 30° C ~ + 70° C;

                                 installation : - 5° C ~ + 50° C
.
Min. bending radius     : 10 x D.

Insulation resistance     : min. 5000 MΩ/km.

Capacitance unbalance : (1 kHz) : max. 500 pF/500 m.
 
RE-2Y(St)YQY-fl MP 70° C - CU/PE/OSCR/PVC/SWB/PVC - PE insulated, collective screened, steel wire braided, PVC sheathed instrumentation cable 300 V
 
Technical data and tests
 
Conductor resistance : 0,50 mm² : 36,7 Ω/km.
                               0,75 mm² : 25,0 Ω/km;
                                1,0 mm² : 18,5 Ω/km;
                                1,3 mm² : 14,2 Ω/km;
                                1,5 mm² : 12,3 Ω/km.
Mutual Capacitance  :            ≤ 4 pairs                all other pairs

                             0,50 mm² : max. 115 pF/m,   max. 90 pF/m; 
                             0,75 mm² : max. 115 pF/m,   max. 90 pF/m; 
                              1,0 mm² : max. 115 pF/m,   max. 90 pF/m;
                              1,3 mm² : max. 120 pF/m,   max. 105 pF/m
                              1,5 mm² : max. 120 pF/m,   max. 105 pF/m.
L / R (ratio) (max.)  : 0,50 mm² : 25 µH/Ω;
                              0,75 mm² : 25 µH/Ω;
                                1,0 mm² : 25 µH/Ω;

                                1,3 mm² : 40 µH/Ω;
                                1,5 mm² : 40 µH/Ω.
Insulation thickness  : 0,50 mm² : 0,40 mm;
                              0,75 mm² : 0,40 mm;

                                1,0 mm² : 0,40 mm;
 
                               1,3 mm² : 0,45 mm;
                          
      1,5 mm² : 0,45 mm.
 
 
RE-2Y(St)YQY-fl MP 70° C - CU/PE/OSCR/PVC/SWB/PVC - PE insulated, collective screened, steel wire braided, PVC sheathed instrumentation cable 300 V
 
Standards
 

Design             : DIN EN 50288-7.

Conductors       : IEC 60228 class 2, DIN EN 60228 class 2.

Insulation         : EN 50290-2-23.

Inner sheath      : EN 50290-2-22.

Outer sheath      : EN 50290-2-22.

Flame retardancy: IEC 60332-1 & EN 60332-1.
 
RE-2Y(St)YQY-fl MP 70° C - CU/PE/OSCR/PVC/SWB/PVC - PE insulated, collective screened, steel wire braided, PVC sheathed instrumentation cable 300 V
 
Applications


These cables are used for transmission of analogue and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc... .
Instrumentation cables are not allowed for direct connection to a low impedance source, e.g. public mains electricity supply.
With blue sheath it is suitable for intrinsically safe systems.
The armour above the sheath, steel wire braid serves as protection against mechanical traverse loads and act as a magnetic screen against interference.
The galvanised steel wires are free of corrosion and oxidation.
They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.