RE-2Y(St)HSWAH-TIMF 70° C - CU/PE/ISCR/OSCR/LSZH/SWA/LSZH Maximize

RE-2Y(St)HSWAH-TIMF 70° C - CU/PE/ISCR/OSCR/LSZH/SWA/LSZH

RE-2Y(St)HSWAH-TIMF 70° C - CU/PE/ISCR/OSCR/LSZH/SWA/LSZH 
- PE insulated, armoured, HFFR sheathed instrumentation cable 300 V
 
Construction

Conductor           : plain copper wire, stranded.

Insulation            : PE compound, (RE-2Y….).


TIMF construction : polyester tape above the triple, AL-PES tape
                           over solid tinned copper drain wire, 0,60 mm. 

Separator            : polyester tape.

Screen                : AL-PES tape over tinned copper drain
                           wire 0,50 mm².

Inner sheath        : HFFR compound.

Armour               : galvanized round steel wire.

Outer sheath        : HFFR compound.

Sheath colour      : RAL 9005, black or RAL 5015, blue.
 
* For detailed information please consult the complete data sheet.

More details

RE-2Y(St)HSWAH-TIMF 70° C - CU/PE/ISCR/OSCR/LSZH/SWA/LSZH 
- PE insulated, armoured, HFFR sheathed instrumentation cable 300 V
 
Technical data and tests

Rated voltage                    : 300 V.

Test voltage                      : Urms core-core : 1500 V;

                                        Urms core-screen : 1500 V.

Temperature range             : operation   : - 30° C ~ + 70° C;

                                        installation :   - 5° C ~ + 50° C.

Min. bending radius           : 10 x D.

 
RE-2Y(St)HSWAH-TIMF 70° C - CU/PE/ISCR/OSCR/LSZH/SWA/LSZH 
- PE insulated, armoured, HFFR sheathed instrumentation cable 300 V
 
Technical data and tests

Insulation resistance          : min. 5000 MΩ/km.
Insulation thickness           : 0,50 mm² : 0,40 mm;
                                       0,75 mm² : 0,40 mm;

                                         1,0 mm² : 0,40 mm; 

                                         1,3 mm² : 0,45 mm;
                                         1,5 mm² : 0,45 mm;

Conductor resistance         : 0,50 mm² : 36,7 Ω/km;

                                       0,75 mm² : 25,0 Ω/km;

                                         1,0 mm² : 18,5 Ω/km;
                                         1,3 mm² : 14,2 Ω/km;

                                         1,5 mm² : 12,3 Ω/km.

L/R (ratio) (max)              : 0,50 mm² : 25 µH/Ω;
                                       0,75 mm² : 25 µH/Ω;

                                         1,0 mm² : 25 µH/Ω;

                                         1,3 mm² : 40 µH/Ω;
                                         1,5 mm² : 40 µH/Ω.

Mutual capacitance (1 kHz) : max. 120 pF/m.

RE-2Y(St)HSWAH-TIMF 70° C - CU/PE/ISCR/OSCR/LSZH/SWA/LSZH 
- PE insulated, armoured, HFFR sheathed instrumentation cable 300 V
Standards


Design                 : DIN EN 50288-7.

Conductor            : IEC 60228 class 2, DIN EN 60228 class 2.

Insulation             : EN 50290-2-23.

Inner/Outer sheath : EN 50290-2-27.

Armour                 : EN 10257-1.

Flame test             : IEC 60332-1 & DIN EN 60332-1,

                            IEC 60332-3 & DIN EN 50266-2-4.

Halogen-free test    : IEC 60754-1/2 & DIN EN 50267-2.

Smoke density test : IEC 61034-2 & DIN EN 61034-2.
 
RE-2Y(St)HSWAH-TIMF 70° C - CU/PE/ISCR/OSCR/LSZH/SWA/LSZH 
- PE insulated, armoured, HFFR sheathed instrumentation cable 300 V
 
Applications


These cables are used for transmission of analogue and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc...
These cables are used in environments which have no corrosive gases emitted in the event of fire.
In case of fire, these cables inhibit the propagation of the flames whereby the development of smoke is extremely low.
Instrumentation cables are not allowed for direct connection to low impedance sources, e.g. public mains electricity supply.
With blue sheath it is suitable for intrinsically safe systems.
The armour above the inner sheath protects the cable from mechanical shocks.
These cables are recommended for direct burial.
They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.