Categories

RE-Y(St)Y-fl TIMF    70° C
 - CU/PVC/ISCR/OSCR/PVC
 Maximize

RE-Y(St)Y-fl TIMF 70° C
 - CU/PVC/ISCR/OSCR/PVC


RE-Y(St)Y-fl TIMF 70° C
 - CU/PVC/ISCR/OSCR/PVC
 - Multi-triple, PVC insulated, screened, PVC sheathed instrumentation cable 500 V
 
Construction
 

Conductor            : plain copper wire, stranded.
Insulation            : PVC compound, 70° C.
TIMF construction : polyester tape above the triple, AL-PES tape over solid
                           tinned copper drain wire, 0,60 mm.
Separator            : polyester tape.
Screen                : AL-PES tape over stranded tinned copper drain
                           wire 0,50 mm².
Outer sheath        : PVC compound, 70° C.

Sheath colour      : RAL 9005, black or RAL 5015, blue.
 
*Please check the data sheet for detailed information.

More details

RE-Y(St)Y-fl TIMF 70° C
 - CU/PVC/ISCR/OSCR/PVC
 - Multi-triple, PVC insulated, screened, PVC sheathed instrumentation cable 500 V
 
Technical data and tests
 

Rated voltage                     : 500 V.

Test votage                       : Urms core-core   : 2000 V;
                                         Urms core-screen: 2000 V. 

Temperature range              : operation   : - 30° C ~ + 70° C;
                                          installation :  - 5° C ~ + 50° C.
Min. bending radius             : 7,5 x D.
Capacitance unbalance         : (1 kHz) : max. 500 pF/500 m.

Insulation resistance (20° C) : min. 100 MΩ/km.
 
RE-Y(St)Y-fl TIMF 70° C
 - CU/PVC/ISCR/OSCR/PVC
 - Multi-triple, PVC insulated, screened, PVC sheathed instrumentation cable 500 V
 
Technical data and tests


Conductor resistance (20° C) : 0,50 mm² : 36,7 Ω/km;
                                          0,75 mm² : 25,0 Ω/km;
                                            1,0 mm² : 18,5 Ω/km;
                                            1,3 mm² : 14,2 Ω/km;
                                            1,5 mm² : 12,3 Ω/km.
Mutual Capacitance (1kHz) :  ≤ 4 pairs                  all other pairs

                          0,50 mm² : max. 160 pF/m      max. 160 pF/m;
                          0,75 mm² : max. 160 pF/m      max. 160 pF/m;
                            1,0 mm² : max. 160 pF/m      max. 160 pF/m;
                            1,3 mm² : max. 170 pF/m      max. 170 pF/m;
                            1,5 mm² : max. 170 pF/m      max. 170 pF/m.
L / R (ratio) (max.)         : 0,50 mm² : 25 µH/Ω;
                                     0,75 mm² : 25 µH/Ω;
                                       1,0 mm² : 25 µH/Ω;

                                       1,3 mm² : 40 µH/Ω;
                                       1,5 mm² : 40 µH/Ω.

RE-Y(St)Y-fl TIMF 70° C
 - CU/PVC/ISCR/OSCR/PVC
 - Multi-triple, PVC insulated, screened, PVC sheathed instrumentation cable 500 V
 
Standards


Design                     : DIN EN 50288-7.

Insulation                 : EN 50290-2-21.

Conductor                : IEC 60228 class 2, DIN EN 60228 class 2.

Flame retardance tes  : IEC 60332-1 & EN 60332-1.

Outer sheath             : EN 50290-2-22.

RE-Y(St)Y-fl TIMF 70° C
 - CU/PVC/ISCR/OSCR/PVC
 - Multi-triple, PVC insulated, screened, PVC sheathed instrumentation cable 500 V
 
Applications


These cables are used for transmission of analogue and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc... .
Instrumentation cables are not allowed for direct connection to a low impedance source, e.g. public mains electricity supply.
Where endurance at 105° C is needed, RE-Yw(St)Yw-TIMF cables are suitable.
With blue sheath it is suitable for intrinsically safe systems.
These cables are not recommended for direct burial.
They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.

All Rights Reserved Halley Cables © 2006 - 2024