Categories

RE-Y(St)Y-fl MP 70° C - CU/PVC/OSCR/PVC Maximize

RE-Y(St)Y-fl MP 70° C - CU/PVC/OSCR/PVC

RE-Y(St)Y-fl MP 70° C - CU/PVC/OSCR/PVC - Single & multi-pair, PVC insulated, screened, PVC sheathed instrumentation cable 300 V
 
Construction
 
Conductor            : plain copper wire, stranded.

Insulation             : PVC compound, 70° C.

Core identification : black / white cores numbered 1-1, 2-2,…
Upon request        : colour coded according to IEC 60189-2.
Pair                     : two conductors twisted to a pair.
Lay-up                 : pairs laid up in layers of optimum pitch.
Separator             : polyester tape.
Screen                 : AL-PES tape over stranded tinned copper drain
                            wire 0,50 mm².

Outer sheath         : PVC compound, 70° C.

Sheath colour        : RAL 9005, black or RAL 5015, blue.

More details

RE-Y(St)Y-fl MP 70° C - CU/PVC/OSCR/PVC - Single & multi-pair, PVC insulated, screened, PVC sheathed instrumentation cable 300 V
 
Technical data and tests

Rated voltage                : 300 V.

Test voltage                  : Urms core-core     : 1500 V;

                                     Urms core-screen : 1500 V.

Temperature range          : operation   : - 30° C ~ + 70° C;

                                      installation :   - 5° C ~ + 50° C.

Min. bending radius         : 7.5 x D.
 
RE-Y(St)Y-fl MP 70° C - CU/PVC/OSCR/PVC - Single & multi-pair, PVC insulated, screened, PVC sheathed instrumentation cable 300 V
 
Technical data and tests


Insulation resistance         : min. 100 MΩ/km.

Capacitance unbalanced   : (1 kHz) : max. 500 pF/500 m.
Insulation thickness         : 0,50 mm² : 0,40 mm;
                                      0,75 mm² : 0,40 mm;

                                        1,0 mm² : 0,40 mm;

                                        1,3 mm² : 0,45 mm;
                                        1,5 mm² : 0,45 mm.

Conductor resistance        : 0,50 mm² : 36,7 Ω/km;

                                      0,75 mm² : 25,0 Ω/km;

                                        1,0 mm² : 18,5 Ω/km;
                                        1,3 mm² : 14,2 Ω/km;

                                        1,5 mm² : 12,3 Ω/km.
L/R (ratio) (max)             : 0,50 mm² : 25 µH/Ω;
                                      0,75 mm² : 25 µH/Ω;

                                        1,0 mm² : 25 µH/Ω;

                                        1,3 mm² : 40 µH/Ω;
                                        1,5 mm² : 40 µH/Ω.

Mutual capacitance (1 kHz):         ≤ 4 pairs                           all other pairs

                                      0,50 mm² : max. 190 pF/m;         max. 150 pF/m;
                                      0,75 mm² : max. 190 pF/m;         max. 150 pF/m;
                                        1,0 mm² : max. 190 pF/m;         max. 150 pF/m;
                                        1,3 mm² : max. 200 pF/m;         max. 150 pF/m;
                                        1,5 mm² : max. 200 pF/m.         max. 150 pF/m.
 
RE-Y(St)Y-fl MP 70° C - CU/PVC/OSCR/PVC - Single & multi-pair, PVC insulated, screened, PVC sheathed instrumentation cable 300 V
 
Standards


Design               : DIN EN 50288-7.

Conductor          : IEC 60228 class 2, DIN EN 60228 class 2.

Insulation           : EN 50290-2-21.

Outer sheath       : EN 50290-2-22. 

Flame retardancy : IEC 60332-1 & EN 60332-1.
 
RE-Y(St)Y-fl MP 70° C - CU/PVC/OSCR/PVC - Single & multi-pair, PVC insulated, screened, PVC sheathed instrumentation cable 300 V
 
Applications


These cables are used for transmission of analogue and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc... .
Instrumentation cables are not allowed for direct connection to a low impedance source, e.g. public mains electricity supply.
Where endurance at 105° C is needed, RE-Yw(St)Yw cables are suitable.
With blue sheath it is suitable for intrinsically safe systems.
These cables are not recommended for direct burial.
They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.

All Rights Reserved Halley Cables © 2006 - 2024