Categories

RE-Y(St)Y-fl-TIMF 70° C - CU/PVC/ISCR/OSCR/PVC/SWA/PVC Maximize

RE-Y(St)Y-fl-TIMF 70° C - CU/PVC/ISCR/OSCR/PVC/SWA/PVC

RE-Y(St)Y-fl-TIMF 70° C - CU/PVC/ISCR/OSCR/PVC/SWA/PVC - PVC insulated, screened, PVC sheathed instrumentation cable 300 V
 
Construction
 
Conductor           : plain copper wire, stranded.

Insulation            : PVC compound, 70° C.

Triple                  : three conductors twisted to a triple.
TIMF construction : polyester tape above the triple, AL-PES tape over solid
                           tinned copper drain wire, 0,60 mm.
Separator            : polyester tape.
Screen                : AL-PES tape over stranded tinned copper drain 
                           wire 0,50 mm².

Outer sheath        : PVC compound, 70° C.

Sheath colour      : RAL 9005, black or RAL 5015, blue.

* Complete information available in the data sheet of this cable.

More details

RE-Y(St)Y-fl-TIMF 70° C - CU/PVC/ISCR/OSCR/PVC/SWA/PVC - PVC insulated, screened, PVC sheathed instrumentation cable 300 V
 
Technical data and tests

Rated voltage                   : 300 V.

Test voltage                     : Urms core-core    : 1500 V;

                                       Urms core-screen : 1500 V.

Temperature range            : operation   : - 30° C ~ + 70° C;
                                        installation :   - 5° C ~ + 50° C.

Min. bending radius           : 7.5 x D.
 
RE-Y(St)Y-fl-TIMF 70° C - CU/PVC/ISCR/OSCR/PVC/SWA/PVC - PVC insulated, screened, PVC sheathed instrumentation cable 300 V
 
Technical data and tests


Insulation resistance          : min. 100 MΩ/km.

Capacitance unbalanced     : (1 kHz) : max. 500 pF/500 m.
Insulation thickness           : 0,50 mm² : 0,40 mm;
                                        0,75 mm² : 0,40 mm;

                                          1,0 mm² : 0,40 mm;

                                          1,3 mm² : 0,45 mm;
                                          1,5 mm² : 0,45 mm.

Conductor resistance          : 0,50 mm² : 36,7 Ω/km;

                                        0,75 mm² : 25,0 Ω/km;

                                          1,0 mm² : 18,5 Ω/km;
                                          1,3 mm² : 14,2 Ω/km;

                                          1,5 mm² : 12,3 Ω/km.

L/R (ratio) (max)               : 0,50 mm² : 25 µH/Ω;
                                        0,75 mm² : 25 µH/Ω;

                                          1,0 mm² : 25 µH/Ω;
                                          1,3 mm² : 40 µH/Ω;
                                          1,5 mm² : 40 µH/Ω.

Mutual capacitance (1 kHz) : 0,50 mm² : max. 190 pF/m;
                                        0,75 mm² : max. 190 pF/m;
                                          1,0 mm² : max. 190 pF/m;
                                          1,3 mm² : max. 200 pF/m;
                                          1,5 mm² : max. 200 pF/m.
 
RE-Y(St)Y-fl-TIMF 70° C - CU/PVC/ISCR/OSCR/PVC/SWA/PVC - PVC insulated, screened, PVC sheathed instrumentation cable 300 V
 
Standards

Design               : DIN EN 50288-7.

Conductor          : IEC 60228 class 2, DIN EN 60228 class 2.

Insulation           : EN 50290-2-21.

Outer sheath       : EN 50290-2-22. 

Flame retardancy : IEC 60332-1 & EN 60332-1.
 
RE-Y(St)Y-fl-TIMF 70° C - CU/PVC/ISCR/OSCR/PVC/SWA/PVC - PVC insulated, screened, PVC sheathed instrumentation cable 300 V
 
Applications


These cables are used for transmission of analogue and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc... .
Instrumentation cables are not allowed for direct connection to a low impedance source, e.g. public mains electricity supply.
Where endurance at 105° C is needed, RE-Yw(St)Yw-TIMF cables are suitable.
With blue sheath it is suitable for intrinsically safe systems.
These cables are not recommended for direct burial.