RE-2G(St)HSWAH-CI FE180 
- CU/SH/OSCR/LSZH/SWA/LSZH Maximize

RE-2G(St)HSWAH-CI FE180 
- CU/SH/OSCR/LSZH/SWA/LSZH

RE-2G(St)HSWAH-CI FE180 
- CU/SH/OSCR/LSZH/SWA/LSZH - Silicone insulated, screened, armoured, HFFR sheathed instrumentation cable 500 V
 
Construction
 

Conductor      : stranded copper wires, class 2.

Insulation       : special silicone rubber compound.
Triple             : three conductors twisted to a triple.

Lay-up           : triples laid up in layers of optimum pitch.
Separator       : polyester tape.
Screen           : AL-PES tape over stranded tinned copper
                      drain wire 0,50 mm².
Inner sheath  : HFFR compound.

Armour          : galvanized round steel wire.

Outer sheath  : HFFR compound.
Sheath colour : RAL 9005, black or RAL 5015, blue.

*Please check the data sheet for detailed information.

More details

RE-2G(St)HSWAH-CI FE180 
- CU/SH/OSCR/LSZH/SWA/LSZH - Silicone insulated, screened, armoured, HFFR sheathed instrumentation cable 500 V
 
Technical data and tests


Rated voltage          : 500 V.
Test voltage            : Urms core-core   : 2000 V;
  
                                Urms core-screen : 2000 V.
Temperature range  : operation   : - 30° C ~ + 90° C;
                                installation :   - 5° C ~ + 50° C.
Min. bending radius : 10 x D.
 
RE-2G(St)HSWAH-CI FE180 
- CU/SH/OSCR/LSZH/SWA/LSZH - Silicone insulated, screened, armoured, HFFR sheathed instrumentation cable 500 V

Technical data and tests

Conductor resistance (20° C) : 0,50 mm² : 36,7 Ω/km;
                                          0,75 mm² : 25,0 Ω/km;
                                            1,0 mm² : 18,5 Ω/km;
                                            1,3 mm² : 14,2 Ω/km;
                                            1,5 mm² : 12,3 Ω/km.
Mutual capacitance (1 kHz) :         ≤ 4 pairs                           all other pairs

                                          0,50 mm² : max. 150 pF/m;       max. 100 pF/m;

                                          0,75 mm² : max. 150 pF/m;       max. 100 pF/m;
                                            1,0 mm² : max. 150 pF/m;       max. 100 pF/m;

                                            1,3 mm² : max. 165 pF/m;       max. 120 pF/m;
                                            1,5 mm² : max. 165 pF/m.       max. 120 pF/m.

L / R (ratio) (max.)             : 0,50 mm² : 25 µH/Ω;
                                         0,75 mm² : 25 µH/Ω;
                                           1,0 mm² : 25 µH/Ω;
                                           1,3 mm² : 40 µH/Ω;
                                       
    1,5 mm² : 40 µH/Ω.
Insulation resistance (20° C)  : min. 300 MΩ/km.

*Special Design :  Sunlight resistance : (UL 1581 section 1200)
  
                                 Oil resistance : (ICEA S-82-552)

*Please see the data sheet for details.
  
RE-2G(St)HSWAH-CI FE180 
- CU/SH/OSCR/LSZH/SWA/LSZH - Silicone insulated, screened, armoured, HFFR sheathed instrumentation cable 500 V
 
Standards

Design                 : EN 50288-7.

Conductor            : IEC 60228 class 2, DIN EN 60228 class 2.

Inner sheath         : EN 50290-2-27.

Armour                : EN 10257-1.
Outer sheath        : EN 50290-2-27.

Flame test            : IEC 60332-1 & DIN EN 60332-1.
                             IEC 60332-3 & DIN EN 50266-2-4.
Smoke density      : IEC 61034-2 & DIN EN 61034-2.
Halogen-free        : IEC 60754-1/2 & DIN EN 50267-2.

Circ. integrity (CI) : IEC 60331, VDE 0472-814;
  BS 6387 cat. CWZ. 
 
RE-2G(St)HSWAH-CI FE180 
- CU/SH/OSCR/LSZH/SWA/LSZH - Silicone insulated, screened, armoured, HFFR sheathed instrumentation cable 500 V
 
Applications


These cables are used for transmission of analogue and digital signals in instrumentation and control systems at chemistry andpetrochemistry industry plants, power plants, natural gas and petroleum plants, etc...
These cables are used in a fixed operating mode, and can continue the supply of power under existing fire conditions and in environments which have no corrosive gases emitted in the event of fire.
In case of fire, these cables inhibit the propagation of the flames and the development of smoke is extremely low.
Instrumentation cables are not allowed for direct connection to a low impedance source, e.g. public mains electricity supply.
With blue sheath it is suitable for intrinsically safe systems.
These cables are not recommended for direct burial.
They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.