RE-2Y(St)H-PIMF 70° C
- CU/PE/ISCR/OSCR/LSZH - PE insulated, screened, HFFR sheathed instrumentation cable 500 V Technical data and tests
Rated voltage : 500 V.
Test voltage : Urms core-core : 2000 V;
Urms core-screen : 2000 V.
Temperature range : operation : - 30° C ~ + 70° C;
installation : - 5° C ~ + 50° C.
Min. bending radius : 7.5 x D.
Insulation resistance : min. 5000 MΩ/km. RE-2Y(St)H-PIMF 70° C
- CU/PE/ISCR/OSCR/LSZH - PE insulated, screened, HFFR sheathed instrumentation cable 500 VTechnical data and tests
Insulation thickness : 0,50 mm² : 0,40 mm; 0,75 mm² : 0,40 mm;
1,0 mm² : 0,40 mm;
1,3 mm² : 0,45 mm; 1,5 mm² : 0,45 mm.
Conductor resistance : 0,50 mm² : 36,7 Ω/km;
0,75 mm² : 25,0 Ω/km;
1,0 mm² : 18,5 Ω/km; 1,3 mm² : 14,2 Ω/km;
1,5 mm² : 12,3 Ω/km.
L/R (ratio) (max) : 0,50 mm² : 25 µH/Ω; 0,75 mm² : 25 µH/Ω;
1,0 mm² : 25 µH/Ω;
1,3 mm² : 40 µH/Ω; 1,5 mm² : 40 µH/Ω.
Mutual capacitance (1 kHz) : max 100 pF/m.
RE-2Y(St)H-PIMF 70° C
- CU/PE/ISCR/OSCR/LSZH - PE insulated, screened, HFFR sheathed instrumentation cable 500 V
Standards
Design : DIN EN 50288-7.
Conductor : IEC 60228 class 2, DIN EN 60228 class 2.
Insulation : EN 50290-2-23.
Outer sheath : EN 50290-2-27.
Flame test : IEC 60332-1 & EN 60332-1;
IEC 60332-3 & DIN EN 50266-2-4.
Smoke density : IEC 61034-2 & DIN EN 61034-2.
Halogen-free : IEC 60754-1/2 & DIN EN 50267-2.
RE-2Y(St)H-PIMF 70° C
- CU/PE/ISCR/OSCR/LSZH - PE insulated, screened, HFFR sheathed instrumentation cable 500 V Applications
These cables are used for transmission of analogue and digital signals in instrumentation and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc... These cables are used in the environments which must have no corrosive gases emitted in the event of fire. In case of fire, these cables inhibit the propagation of the flames whereby the development of smoke is extremely low. Instrumentation cables are not allowed for direct connection to a low impedance source, e.g. public mains electricity supply. With blue sheath it is suitable for intrinsically safe systems. These cables are not recommended for direct burial. They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.