RE-Y(St)Y-fl 70° C
- CU/PVC/OSCR/PVC - PVC insulated, collective screened, PVC sheathed instrumentation and control cable 500 V Technical data and tests
Rated voltage : 500 V.Test voltage : Urms core-core : 2000 V;
Urms core-screen : 2000 V.Temp. range : operation : - 30° C ~ + 70° C; installation : - 5° C ~ + 50° C.
Min. bending radius : 7.5 x D.
RE-Y(St)Y-fl 70° C
- CU/PVC/OSCR/PVC - PVC insulated, collective screened, PVC sheathed instrumentation and control cable 500 V
Technical data and tests
Conductor resistance (20° C) : 0,50 mm² : 36,0 Ω/km;
0,75 mm² : 24,5 Ω/km;
1,0 mm² : 18,1 Ω/km;
1,3 mm² : 13,9 Ω/km;
1,5 mm² : 12,1 Ω/km;
2,5 mm² : 7,4 Ω/km.
L / R (ratio) (max.) : 0,50 mm² : 25 µH/Ω;
0,75 mm² : 25 µH/Ω;
1,0 mm² : 25 µH/Ω;
1,3 mm² : 40 µH/Ω;
1,5 mm² : 40 µH/Ω;
2,5 mm² : 60 µH/Ω.
Insulation resistance (20° C) : min. 100 MΩ/km.
Mutual capacitance : max. 190 pF/m (1 kHz).
RE-Y(St)Y-fl 70° C
- CU/PVC/OSCR/PVC - PVC insulated, collective screened, PVC sheathed instrumentation and control cable 500 V
Standards
Design : EN 50288-7.
Conductor : IEC 60228 class 2, DIN EN 60228 class 2.
Insulation : EN 50290-2-21.
Outer sheath : EN 50290-2-22 (2Y/2X).
Flame test : IEC 60332-1 & DIN EN 60332-1;
IEC 60332-3 & DIN EN 50266-2-4.
RE-Y(St)Y-fl 70° C
- CU/PVC/OSCR/PVC - PVC insulated, collective screened, PVC sheathed instrumentation and control cable 500 V Applications
These cables are used for control purposes (e.g. controlling of pumps, valves or engines) at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc... . Instrumentation cables are not allowed to be directly connected to a low impedance source, e.g. public mains electricity supply. For applications which need heat resistance up to 105° C, RE-Yw(St)Yw cables are suitable. With blue sheath they are suitable for intrinsically safe systems. These cables are not recommended for direct burial. They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.