Categories

RE-2X(St)H 90° C
 - CU/XLPE/OSCR/LSZH Maximize

RE-2X(St)H 90° C
 - CU/XLPE/OSCR/LSZH

RE-2X(St)H 90° C
 - CU/XLPE/OSCR/LSZH - XLPE insulated, collective screened, HFFR sheathed instrumentation and control cables 500 V
 
Construction
 

Conductor             : stranded copper wires.
Insulation             : XLPE compound, (RE-2X….).
Core identification : black cores are numbered (1-2-3...). Other core
                             configurations manufactured upon request.
Lay-up                 : cores laid up in layers of optimum pitch.
Separator             : polyester tape.
Screen                 : AL-PES tape over stranded tinned copper drain
                             wire 0,50 mm².
Outer sheath        : HFFR compound.
Sheath colour       : RAL 9005, black or RAL 5015, blue.

More details

RE-2X(St)H 90° C
 - CU/XLPE/OSCR/LSZH - XLPE insulated, collective screened, HFFR sheathed instrumentation and control cables 500 V
 
Technical data and tests


Rated voltage          : 500 V.
Test voltage            : Urms core-core    : 2000 V;

                              Urms core-screen : 2000 V.
Temperature range  : operation   : - 30° C ~ + 90° C;
                             installation :   - 5° C ~ + 50° C.
Min. bending radius  : 7.5 x D.
 
RE-2X(St)H 90° C
 - CU/XLPE/OSCR/LSZH - XLPE insulated, collective screened, HFFR sheathed instrumentation and control cables 500 V

Technical data and tests

Conductor resistance      : 0,50 mm² : 36,0 Ω/km;
                                    0,75 mm² : 24,5 Ω/km;
                                      1,0 mm² : 18,1 Ω/km;
                                      1,3 mm² : 13,9 Ω/km;
                                      1,5 mm² : 12,1 Ω/km;

                                      2,5 mm² :   7,4 Ω/km.
Insulation resistance      : min. 5000 MΩ/km.
Mutual Capacitance        : max. 120 pF/m.
Capacitance unbalanced : (1 kHz) : max. 500 pF/500 m.
L / R (ratio) (max.)        : 0,50 mm² : 25 µH/Ω;
                                    0,75 mm² : 25 µH/Ω;
                                      1,0 mm² : 25 µH/Ω;

                                      1,3 mm² : 40 µH/Ω;
                                      1,5 mm² : 40 µH/Ω;

                                      2,5 mm² : 60 µH/Ω.
 
RE-2X(St)H 90° C
 - CU/XLPE/OSCR/LSZH - XLPE insulated, collective screened, HFFR sheathed instrumentation and control cables 500 V

Standards


Design                   : EN 50288-7.

Conductor              : IEC 60228 class 2, DIN EN 60228 class 2.
Insulation               : EN 50290-2-29.

Outer sheath           : EN 50290-2-27.

Flame test              : IEC 60332-1 & DIN EN 60332-1
                              IEC 60332-3 & DIN EN 50266-2-4

Smoke density test   : IEC 61034-2 & DIN EN 61034-2

Halogen-free test     : IEC 60754-1/2 & DIN EN 50267-2
 
RE-2X(St)H 90° C
 - CU/XLPE/OSCR/LSZH - XLPE insulated, collective screened, HFFR sheathed instrumentation and control cables 500 V
 
Applications


These cables are used for control purposes (e.g. controlling of pumps, valves or engines) at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc...
These cables are used in environments which must have no corrosive gases emitted in the event of fire.
In case of fire, these cables inhibit the propagation of the flames whereby the development of smoke is extremely low.
Instrumentation cables are not allowed for direct connection to a low impedance source, e.g. public mains electricity supply.
For applications where heat resistance up to 90° C is crucial, RE-2X(St)H cables are suitable.
With blue sheath it is suitable for intrinsically safe systems.
These cables are not recommended for direct burial.
They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.

All Rights Reserved Halley Cables © 2006 - 2024