RE-2X(St)HSWAH 90° C
 - CU/XLPE/OSCR/LSZH/SWA/LSZH Maximize

RE-2X(St)HSWAH 90° C
 - CU/XLPE/OSCR/LSZH/SWA/LSZH

RE-2X(St)HSWAH 90° C
 - CU/XLPE/OSCR/LSZH/SWA/LSZH
 - XLPE insulated, screened, armoured, HFFR sheathed insturmentation and control cables 500 V
 
Construction
 

Conductor           : stranded copper wires, class 2.
Insulation            : XLPE compound, (RE-2X….).
Lay-up                : cores laid up in layers of optimum pitch.
Separator            : polyester tape.
Screen                 : AL-PES tape over stranded tinned copper drain
                            wire 0,50 mm².

Inner sheath        : HFFR compound.

Armour                : galvanized round steel wire.
Outer sheath        : HFFR compound.
Sheath colour       : RAL 9005, black or RAL 5015, blue.
Core identification : black numbered 1-2-3... Other core configurations
                             manufactured upon request.

More details

RE-2X(St)HSWAH 90° C
 - CU/XLPE/OSCR/LSZH/SWA/LSZH
 - XLPE insulated, screened, armoured, HFFR sheathed insturmentation and control cables 500 V
 
Technical data and tests


Rated voltage         : 500 V.
Test voltage           : Urms core-core    : 2000 V;

                               Urms core-screen : 2000 V.
Temperature range : operation   : - 30° C ~ + 90° C;
                               installation :   - 5° C ~ + 50° C.
Min. bending radius : 10 x D.
 
RE-2X(St)HSWAH 90° C
 - CU/XLPE/OSCR/LSZH/SWA/LSZH
 - XLPE insulated, screened, armoured, HFFR sheathed insturmentation and control cables 500 V

Technical data and tests


Conductor resistance (20° C) : 0,50 mm² : 36,0 Ω/km;
                                             0,75 mm² : 24,5 Ω/km;
                                               1,0 mm² : 18,1 Ω/km;
                                               1,3 mm² : 13,9 Ω/km;
                                               1,5 mm² : 12,1 Ω/km;

                                               2,5 mm² :   7,4 Ω/km.
Insulation resistance (20° C)  : min. 5000 MΩ/km.
Mutual capacitance                : max. 120 pF/m.
L / R (ratio) (max.)                : 0,50 mm² : 25 µH/Ω;
                                              0,75 mm² : 25 µH/Ω;
                                               1,0 mm² : 25 µH/Ω;
                                           
    1,3 mm² : 40 µH/Ω;
                                               1,5 mm² : 40 µH/Ω;

                                               2,5 mm² : 60 µH/Ω.
 
RE-2X(St)HSWAH 90° C
 - CU/XLPE/OSCR/LSZH/SWA/LSZH
 - XLPE insulated, screened, armoured, HFFR sheathed insturmentation and control cables 500 V

Standards


Design             : EN 50288-7.

Conductor        : IEC 60228 class 2, DIN EN 60228 class 2.

Insulation        : EN 50290-2-29.

Inner sheath    : EN 50290-2-27.

Armour            : EN 10257-1.

Outer sheath    : EN 50290-2-27.

Flame test       : IEC 60332-1 & DIN EN 60332-1;
                        IEC 60332-3 & DIN EN 50266-2-4.
Smoke density : IEC 61034-2 & DIN EN 61034-2.
Halogen-free   : IEC 60754-1/2 & DIN EN 50267-2.
 
RE-2X(St)HSWAH 90° C
 - CU/XLPE/OSCR/LSZH/SWA/LSZH
 - XLPE insulated, screened, armoured, HFFR sheathed insturmentation and control cables 500 V
 
Applications


These cables are used for control purposes (e.g. controlling of pumps, valves or engines) at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc...
These cables are used in environments which must have no corrosive gases emitted in the event of fire.
In case of fire, these cables inhibit the propagation of the flames whereby the development of smoke is extremely low.
Instrumentation cables are not allowed for direct connection to a low impedance source, e.g. public mains electricity supply.
With blue sheath it is suitable for intrinsically safe systems.
The armour above the inner sheath protects the cable from mechanical shocks.
These cables are not recommended for direct burial.
They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.