RE-2X(St)H-PIMF 90° C - CU/XLPE/ISCR/OSCR/LSZH Maximize

RE-2X(St)H-PIMF 90° C - CU/XLPE/ISCR/OSCR/LSZH

RE-2X(St)H-PIMF 90° C - CU/XLPE/ISCR/OSCR/LSZH - XLPE insulated, HFFR sheathed instrumentation cables 300 V
 
Construction

Conductor             : plain copper wire, stranded.

Insulation             : XLPE compound (RE-2X….).

Core identification : black / white cores numbered 1-1, 2-2,…
Upon request:       : colour coded according to IEC 60189-2.

Pair                      : two conductors twisted to a pair.

Lay-up                 : triples laid up in layers of optimum pitch.

Separator             : polyester tape.

Screen                 : AL-PES tape over tinned copper drain
                            wire 0,50 mm².

Outer sheath        : HFFR compound.

Sheath colour       : RAL 9005, black or RAL 5015, blue.

More details

RE-2X(St)H-PIMF 90° C - CU/XLPE/ISCR/OSCR/LSZH - XLPE insulated, HFFR sheathed instrumentation cables 300 V
 
Technical Data and Tests

Rated voltage                    : 300 V.

Test voltage                      : Urms core-core   : 1500 V;

                                        Urms core-screen : 1500 V.

Temperature range            : operation   : - 30° C ~ + 90° C;

                                        installation :  - 5° C ~ + 50° C.

Insulation resistance          : min. 5000 MΩ/km.

Mutual capacitance (1 kHz) : max. 120 pF/m.

Min. bending radius           : 7,5 x D.
 
 
RE-2X(St)H-PIMF 90° C - CU/XLPE/ISCR/OSCR/LSZH - XLPE insulated, HFFR sheathed instrumentation cables 300 V
Technical data and tests

Insulation thickness       : 0,50 mm² : 0,40 mm;
                                    0,75 mm² : 0,40 mm;

                                     1,0 mm² : 0,40 mm;

                                     1,3 mm² : 0,45 mm; 
                                     1,5 mm² : 0,45 mm.
Conductor resistance   : 0,50 mm² : 36,7 Ω/km;

                                 0,75 mm² : 25,0 Ω/km;

                                   1,0 mm² : 18,5 Ω/km; 
                                   1,3 mm² : 14,2 Ω/km;

                                   1,5 mm² : 12,3 Ω/km.

L/R (ratio) (max)        : 0,50 mm² : 25 µH/Ω; 
                                 0,75 mm² : 25 µH/Ω;

                                   1,0 mm² : 25 µH/Ω;
                               
    1,3 mm² : 40 µH/Ω; 
                                   1,5 mm² : 40 µH/Ω.
 
RE-2X(St)H-PIMF 90° C - CU/XLPE/ISCR/OSCR/LSZH - XLPE insulated, HFFR sheathed instrumentation cables 300 V
 
Standards


Design                       : DIN EN 50288-7.

Conductor                  : IEC 60228 class 2, DIN EN 60228 class 2.

Insulation                   : EN 50290-2-29.

Smoke density test       : IEC 61034-2 & DIN EN 61034-2. 

Flame retardancy test   : IEC 60332-1 & DIN EN 60332-1, 

                                  IEC 60332-3 & DIN EN50266-2-4.

Outer sheath              : EN 50290-2-27. 

Halogen-free test        : IEC 60754-1/2;

                                 DIN EN 50267-2.
 
RE-2X(St)H-PIMF 90° C - CU/XLPE/ISCR/OSCR/LSZH - XLPE insulated, HFFR sheathed instrumentation cables 300 V
 
Applications

These cables are used for transmission of analogue and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc...
These cables are used in the environments which have no corrosive gases are emitted in the event of fire.
In case of fire, these cables inhibit the propagation of the flames whereby the development of smoke is extremely low.
Instrumentation cables are not allowed for direct connection to a low impedance source, e.g. public mains electricity supply.
With blue sheath it is suitable for intrinsically safe systems.
These cables are not recommended for direct burial.
They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.