Categories

RE-2X(St)H-TIMF 90° C -  CU/XLPE/ISCR/OSCR/LSZH
 Maximize

RE-2X(St)H-TIMF 90° C - CU/XLPE/ISCR/OSCR/LSZH


RE-2X(St)H-TIMF 90° C -  CU/XLPE/ISCR/OSCR/LSZH
 - XLPE insulated, screened, HFFR sheathed instrumentation cable 300 V
 
Construction

Conductor            : plain copper wire, stranded.

Insulation             : XLPE compound, (RE-2X….).

Triple                   : three conductors twisted to a triple.

TIMF construction : polyester tape above the triple, AL-PES tape over solid
                             tinned copper drain wire, 0,60 mm.
Lay-up                 : TIMF laid up in layers of optimum pitch.

Separator             : polyester tape.

Screen                 : AL-PES tape over tinned copper drain wire 0,50 mm².

Outer sheath        : HFFR compound.

Sheath colour       : RAL 9005, black or RAL 5015, blue.

More details

RE-2X(St)H-TIMF 90° C -  CU/XLPE/ISCR/OSCR/LSZH
 - XLPE insulated, screened, HFFR sheathed instrumentation cable 300 V
 
Technical data and tests


Rated voltage                    : 300 V.

Test voltage                      : Urms core-core    : 1500 V;

                                         Urms core-screen : 1500 V.

Temperature range            : operation   : - 30° C ~ + 90° C;

                                        installation :   - 5° C ~ + 50° C.

Min. bending radius            : 7,5 x D.
 
RE-2X(St)H-TIMF 90° C -  CU/XLPE/ISCR/OSCR/LSZH
 - XLPE insulated, screened, HFFR sheathed instrumentation cable 300 V
 
Technical data and tests


Insulation resistance          : min. 5000 MΩ/km.
Insulation thickness           : 0,50 mm² : 0,40 mm;
                                        0,75 mm² : 0,40 mm;

                                          1,0 mm² : 0,40 mm;

                                          1,3 mm² : 0,45 mm;
                                          1,5 mm² : 0,45 mm;

Conductor resistance         : 0,50 mm² : 36,7 Ω/km;

                                       0,75 mm² : 25,0 Ω/km;

                                         1,0 mm² : 18,5 Ω/km;
                                         1,3 mm² : 14,2 Ω/km;

                                         1,5 mm² : 12,3 Ω/km.

L/R (ratio) (max)              : 0,50 mm² : 25 µH/Ω;
                                       0,75 mm² : 25 µH/Ω;

                                         1,0 mm² : 25 µH/Ω;

                                         1,3 mm² : 40 µH/Ω;
                                         1,5 mm² : 40 µH/Ω.

Mutual capacitance (1 kHz) : max. 120 pF/m.
 
RE-2X(St)H-TIMF 90° C -  CU/XLPE/ISCR/OSCR/LSZH
 - XLPE insulated, screened, HFFR sheathed instrumentation cable 300 V
 
Standards

Design                   : DIN EN 50288-7.

Conductor              : IEC 6022 class 2, DIN EN 60228 class 2.

Insulation               : EN 50290-2-29.

Outer sheath           : EN 50290-2-27.

Flame retardancy     : IEC 60332-1 & DIN EN 60332-1,

                              IEC 60332-3 & DIN EN 50266-2-4.

Halogen-free test     : IEC 60754-1/2;

                              DIN EN 50267-2.

Smoke density test   : IEC 61034-2 & DIN EN 61034-2.
 
RE-2X(St)H-TIMF 90° C -  CU/XLPE/ISCR/OSCR/LSZH
 - XLPE insulated, screened, HFFR sheathed instrumentation cable 300 V
 
Applications

These cables are used for transmission of analogue and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc...
These cables are used in the environments which must have no corrosive gases emitted in the event of fire.
In case of fire, these cables inhibit the propagation of the flames whereby the development of smoke is extremely low.
Instrumentation cables are not allowed for direct connection to a low impedance source, e.g. public mains electricity supply.
With blue sheath it is suitable for intrinsically safe systems.
These cables are not recommended for direct burial.
They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.

All Rights Reserved Halley Cables © 2006 - 2024