Categories

RE-2X(St)Y-fl-PIMF 90° C - CU/XLPE/ISCR/OSCR/PVC Maximize

RE-2X(St)Y-fl-PIMF 90° C - CU/XLPE/ISCR/OSCR/PVC

RE-2X(St)Y-fl-PIMF 90° C - CU/XLPE/ISCR/OSCR/PVC - XLPE insulated, PVC sheathed instrumentation cable 300 V
 
Construction

Conductor            : plain copper wire, stranded.

Insulation             : XLPE compound, (RE-2X….).

Pair                     : two conductors twisted to a pair.

PIMF construction : polyester tape above the pair, AL-PES tape over solid
                           tinned copper drain wire, 0,60 mm.
                            Upon request: stranded 0,50 mm² copper drain wire.

Separator             : polyester tape.

Screen                 : AL-PES tape over tinned copper drain wire 0,50 mm².

Outer sheath         : PVC compound, 90° C.
Sheath colour       : RAL 9005, black or RAL 5015, blue.

More details

RE-2X(St)Y-fl-PIMF 90° C - CU/XLPE/ISCR/OSCR/PVC - XLPE insulated, PVC sheathed instrumentation cable 300V

Technical data and tests

Rated voltage               : 300 V.

Test voltage                 : Urms core-core   : 1500 V;

                                   Urms core-screen : 1500 V.

Temperature range        : operation   : - 30° C ~ + 90° C;

                                   installation :   - 5° C ~ + 50° C.

Min. bending radius       : 7.5 x D.
 
RE-2X(St)Y-fl-PIMF 90° C - CU/XLPE/ISCR/OSCR/PVC - XLPE insulated, PVC sheathed instrumentation cable 300V
 
Technical data and tests


Insulation resistance      : min. 5000 MΩ/km.

Capacitance unbalanced : (1 kHz) : max. 500 pF/500 m.
Insulation thickness       : 0,50 mm² : 0,40 mm;
                                    0,75 mm² : 0,40 mm;

                                      1,0 mm² : 0,40 mm;

                                      1,3 mm² : 0,45 mm;
                                      1,5 mm² : 0,45 mm;

Conductor resistance      : 0,50 mm² : 36,7 Ω/km;
                                  
  0,75 mm² : 25,0 Ω/km;

                                      1,0 mm² : 18,5 Ω/km;
                                      1,3 mm² : 14,2 Ω/km;
                                  
    1,5 mm² : 12,3 Ω/km.

L/R (ratio) (max)           : 0,50 mm² : 25 µH/Ω;
                                    0,75 mm² : 25 µH/Ω;

                                      1,0 mm² : 25 µH/Ω;

                                      1,3 mm² : 40 µH/Ω;
                                      1,5 mm² : 40 µH/Ω.

Mutual capacitance         : max 120 pF/m (1 kHz).
 
RE-2X(St)Y-fl-PIMF 90° C - CU/XLPE/ISCR/OSCR/PVC - XLPE insulated, PVC sheathed instrumentation cable 300V
 
Standards

Design               : DIN EN 50288-7.

Conductor          : IEC 60228 class 2, DIN EN 60228 class 2.

Insulation           : EN 50290-2-29.

Outer sheath       : EN 50290-2-22.

Flame retardancy : IEC 60332-1 & DIN EN 60332-1.
 
RE-2X(St)Y-fl-PIMF 90° C - CU/XLPE/ISCR/OSCR/PVC - XLPE insulated, PVC sheathed instrumentation cable 300V
 
Applications

These cables are used for transmission of analogue and digital signals in instrumentation and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc... .
Instrumentation cables are not allowed for direct connection to a low impedance source, e.g. public mains electricity supply.
With blue sheath it is suitable for intrinsically safe systems.
These cables are not recommended for direct burial.
They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.

All Rights Reserved Halley Cables © 2006 - 2024